PROBLEM CAUSE SOLUTION
Compressor does not start be-
cause of protecve devices
Increase in discharge pressure
Low inlet pressure
Incorrect power supply
Incorrect wiring
Incorrect working condions
Thermal protecon intervenon
Check
Damaged pressure switch Repalce
High exhaust pressure
High outside air temperature
High water return temperature
Air in the hydraulic circuit
Refrigerant gas charge too high
Check
Poor air ow
Poor water ow rate
Check the fan and pump operaon
Low exhaust pressure
High outdoor air temperature
Low plant return water temperature
Residual humidity in the cooling circuit
Air in the hydraulic circuit
Insucient refrigerant gas charge
Check
High sucon pressure
High outdoor air temperature
Low plant return water temperature
Expansion valve remains too opened / dam-
aged
Check
Low compressor sucon pressure
Low outdoor air temperature
Low plant return water temperature
Expansion valve remains too closed / clogged/
damaged
Dirty plate heat exchanger
Check
Low air ow rate
Low water ow rate
Check the fan and pump operaon