Specifications
Sensor Operating
Temperature
32°F to 122°F (0°C to 50°C).
Storage Temperature -22°F to 122°F (-30°C to 50°C).
Storage and Operating
Humidity Range
0% to 95%, non-condensing.
Temperature Control
Accuracy
+/-0.9°F (+/-0.5°C) @ 70F (21°C) typical calibrated.
Temperature Sensor
Resolution
+/-0.2°F (+/-0.1°C).
Room Air Temperature
Display Range
-40°F to 122°F (- 40°C to 50°C).
Occupied/Unoccupied
Setpoint Range
• Cooling: 60°F to 85°F (15.5°C to 29.4°C).
• Heating: 55°F to 80°F (12.7°C to 26.6°C).
Heating/Cooling Setpoint
Minimum Deadband
2°F to 10°F (1.0°C to 5.5°C).
Power Supply 24 Vdc / 24 Vac (19-30 Vac), 50 / 60 Hz, Class 2.
Power Wire 18 AWG or larger
Power Consumption 4 VA.
Housing
• Polycarbonate/ABS blend.
•UV protected.
• U.L. 94–5VA flammability rating.
• Suitable for application in a plenum.
Weight 0.75 lb. (0.34 kg).
Mounting 3.24 in (8.26 cm) for 2 mounting screws (supplied).
Communication Wire
•22 AWG or Larger.
• Two conductor shielded twisted pair with drain wire.
• Characteristic impedance between 100 and 130 ohms.
• Capacitance between conductors, less than 100 pF per meter (30 pF per foot).
• Capacitance between conductors and shield, less than 200 pF meter (60 pF per foot).
Load Shed Input Dry contact
Safety Standards
• LVD Directive 2006/95/EC.
• EN60950–a: 2006/A2:2013.
• U.L. 873 CSA C22.2 No. 24–93.
EMC Standards
• EMC Directive 2004/108/EC.
• IEC 61326–1: 2005.
• FCC 15 Subpart B, Class A.
• ICES-003.
RoHS Compliance Enclosure and components are RoHS compliant (RoHS 2002/95/EC).
WARNING
Cancer and Reproductive Harm!
This product can expose you to chemicals including
lead and bisphenol A (BPA), which are known to the
State of California to cause cancer and birth defects or
other reproductive harm. For more information, go to
www.P65Warnings.ca.gov.