27 BAS-SVN028K-EN
ReliaTel Field Upgrade Procedure
When ReliaTel controlled equipment is modified in the
field in a manner that changes the point configuration of
the unit, the BCI-R must interrogate the ReliaTel control
system to learn the new points list of the equipment. This
action only takes place during initial power-up after the
BCI-R device memory has been cleared. The new point list
is permanently stored in the memory of the BCI-R device.
BCI-R Initialization Procedure
Use the BACnet Setup Tool to clear the controller and
restore to factory defaults.
1. Navigate to the Controller Settings screen.
2. Click within the light gray area of the bottom left of the
screen just above the “Connected” indicator.
The Clear Controller button appears at the top right of
the screen.
3. Click Clear Controller.
A message appears stating that the configuration will
be reset (deleted).
4. Click OK.
When the controller is cleared, the Select Device Units
message box appears.
5. Click OK and then expand the Controller Units box on
the Controller Settings screen.
6. Select the units (SI, IP, or Custom).
Note: This selection defaults to Custom after clearing
the controller. If you want to use Custom,
ensure that all unit options are set correctly.
7. Click Save.