Menu Definitions
BAS-SVN028K-EN 23
Clock, Schedule, Setpoints, and
Options
Clock
Defines the time and date used with the programmable time schedule function.:
•Time format
AM-PM: 12 hour format (displays as 8:00 PM).
24 Hours: 24 hour form (displays as 20:00 hours).
Time – defines the hour and minute of the current day.
Year – defines the current year.
Month – defines the current month.
Day – defines the current day of current month.
Weekday – displays a day of the week corresponding to the date entered into
the sensor.
Schedule
Defines the time values that are used to determine when to transition from the
current occupancy state to the next state.
Three occupied/unoccupied event pairs are supported. Setting an event to a time
value enables the event. Setting the event to - - : - - disables the event.
Setpoints
Defines the following:
Unocc. cool – the temperature setpoint in use when the equipment is in
cooling mode and occupancy mode is unoccupied.
Occ. cool – the temperature setpoint in use when the equipment is in cooling
mode and occupancy mode is occupied.
Occ. heat – the temperature setpoint in use when the equipment is in heating
mode and occupancy mode is occupied.
Unocc. heat – the temperature setpoint in use when the equipment is in
heating mode and occupancy mode is unoccupied.
(50.0°F to 90.0°F [10.0°C to 32.2°C])
Options
Defines the occupancy commands and schedule type.
Occupancy cmd
Loc. occ.: occupancy is determined by the schedule
Occupied: force occupied mode
Unocc.: force unoccupied mode.
Schedule type
7 days: each day of the week.
5+2: weekdays + weekend.
5+1+1: weekdays + Saturday + Sunday.