Installation Instructions
26 BAS-SVN028K-EN
Symbio 700/800
Zone Sensor Configuration
1
Remove power from the HVAC equipment and apply electrical lock out/tag out
procedures.
2
Symbio controller: Set rotary dials to 0 - 0 - 1.
3
Connect the 24 Volt AC/DC power wires between the zone sensor and Symbio controller.
4
Connect the 2-conductor + shield cable between the zone sensor and Symbio controller.
Note: Communication is polarity sensitive. Ensure that the wires are landed to the correct
terminals.
5
(Optional) Connect motion sensor or space temperature sensor to zone sensor terminals
17 and 18.
9
Apply power to the HVAC equipment.
10
Proceed to the Zone Sensor Configuration checklist.
1
Navigate to menu — 1/2 Network Settings
Confirm the following:
Sens. Address = 2
Unit address = 1
Baud rate = 76,800
Status = Online
2
If Status = Offline
Check communication cable wiring for incorrect termination and reverse polarity.
Confirm the following:
Rotary dial value on the equipment controller = 2.
Cycle power to zone sensor and equipment controller.
3
Navigate to menu — 2/2 Network Instance.
Press the R icon button. The instance value will change to 2.
Press the check-mark icon button. The new value will be saved.
Zone sensor configuration is complete.
4
Navigate to menu — 4/7 Service View.
Confirm the following:
Unit status = Online
If Unit status = Offline repeat the zone sensor configuration process.
If problems persist, contact Trane Technical support (1-877-788-7263).

Other manuals for Trane ReliaTel