Zone Sensor Wiring
BAS-SVN028K-EN 11
Symbio 700 Systems
The zone sensor and the Symbio 700 form a two node
BACnet MS/TP network. Wire the system as shown in the
schematic below.
Note:
• The Symbio 700 controller must be an advanced
version. The controller protocol must be set to BACnet
MS/TP.
• The Symbio 700 controller must be configured for a
single setpoint zone sensor for proper operation by
using the Symbio Service and Installation App:
(Settings > Edit Configuration > Space Controller =
Single Setpoint Zone Sensor)
or Local Display (Utilities > Unit Config > Edit Unit
Config > Space Controller = Single Setpoint Zone
Sensor).