Zone Sensor Wiring
8 BAS-SVN028K-EN
ReliaTel Systems
The zone sensor and the BCI-R form a two-node BACnet
MS/TP network. Wire the system as shown in the
schematic below while adhering to the following
recommendations:
At the RTRM board, terminate the shield wire at J7-
COM terminal. The shield wire may need to be
extended to make this connection. Use an insulated
extension wire to prevent contact with the metal
enclosure and circuit boards.
Set the link switch on the BCI-R to BACnet.
Important: Install a jumper wire between terminals J6-
1 and 2 when the internal temperature
sensor or a sensor wired to terminals 17 and
18 is used.
.