18 BAS-SVN028K-EN
Interface Flowchart, Part 4
There are no field configurable parameters in the Lua
menus. This menu is displayed to confirm that the version
of the sensor is correct for the application.
Note: Sensors that show UC400 are also compatible with
Symbio 400 controllers. Sensors that show Symbio
800 are also compatible with Symbio 700
controllers.
Network
Refer to the Zone Sensor Configuration section at the end
of this document for zone sensor configuration
instructions.
Sens. Address
Defines the BACnet MAC address of the zone
sensor (0-127).
Unit address
Defines the BACnet MAC address of the HVAC
equipment (0-127).
Baud rate
Defines the baud rate of the zone sensor. Default is
76800 (use default value unless directed by Trane
Technical Support).
Status
Indicates if a network is established between the
zone sensor and the HVAC equipment.
2/2 Network
Instance
Defines the BACnet Device ID of the sensor. Tap
to Confirm and Save the value (0 - 4194302).
Tapping R on this screen copies the sensor MAC
address number to the BACnet Device ID field. For
example, if the MAC address = 7, tapping
R sets the
Device ID number to 7.