General Electrical Recommendations
Electrical data
To get the following electrical data details: Refer to General Data tables for each unit confi guration and size.
- Maximum Power input (kW)
- Unit rated amps (Max compr +Fan+Control)
- Unit start up amps (Starting Amps of the largest compr+RLA of 2nd compr+RLA of all fans+ control)
- Compressor Power factor
- Disconnect switch size (A)
- Short Circuit Rating for all sizes =35 kA
For the control of every unit
- Max power input is 1.4 kW
- Max Amps is 3.4 A
Fan data
- Motor AC : I max=4.0 A - P max=1.85 kW
- Motor EC : I max=3.0 A - P max=1.95 kW
Wiring diagrams are shipped with unit and can be found in the unit control panel.
Note : Rating is made for 400 V, 3 phases, 50 Hz power supply.