18-GJ89D1-1F-EN
53
TAMXB0C60V51DB
Heater Model No.
No. of
Circuits
240 Volt 208 Volt
Capacity
Heater
Amps per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
Capacity
Heater
Amps per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
kW BTUH kW BTUH
No Heater 0 - - 7.5 ** 9 15 - - 7.5 ** 9 15
BAYEAAC04++1 1 3.84 13100 16.0 29 30 2.88 9800 13.8 27 30
BAYEAAC05++1 1 4.80 16400 20.0 34 35 3.60 12300 17.3 31 35
BAYEAAC08++1 1 7.68 26200 32.0 49 50 5.76 19700 27.7 44 45
BAYEAAC10++1 1 9.60 32800 40.0 59 60 7.20 24600 34.6 53 60
BAYEAAC10LG3 1-3 PH 9.60 32800 23.1 38 40 7.20 24600 20.0 34 35
BAYEABC15LG3 1-3 PH 14.40 42000 34.6 53 60 10.80 36900 30.0 47 50
BAYEABC15BK1 - Circuit 1
(a)
BAYEABC15BK1 - Circuit 2
2
9.60 32800 40.0 59 60 7.20 24600 34.6 53 60
4.80 16400 20.0 25 25 3.60 12300 17.3 22 25
BAYEABC20BK1 - Circuit 1
BAYEABC20BK1 - Circuit 2
2
9.60 32800 40.0 59 60 7.20 24600 34.6 53 60
9.60 32800 40.0 50 50 7.20 24600 34.6 43 45
BAYEACC25BK1
(b)
- Circuit 1
BAYEACC25BK1 - Circuit 2
BAYEACC25BK1 - Circuit 3
3
9.60 32800 40.0 59 60 7.20 24600 34.6 53 60
9.60 32800 40.0 50 50 7.20 24600 34.6 43 45
4.80 16400 20.0 25 25 3.60 12300 17.3 22 25
Note: ** Motor Amps
(a)
MCA and MOP for circuit 1 contains the motor amps
(b)
Heater not qualified for 208V when installed in horizontal left position without Heat Pump
Note: See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
Note: Heater model numbers may have additional suffix digits.