Table 14. Manual Control settings menu screen: Buttons, available setting options, and status points (continued)
Feature
Current
value
Available setting
options
Status points
Clear Energy Consumption
XXXX kWh
Simplex chillers only:
Clear
Duplex chillers only:
Energy Consumption
Resettable Ckt1, Ckt2
Starter Energy Consump. Resettable
Starter Energy Consump. Last Reset
Starter Energy Consump. NonReset
Oil Pump Control
Note: Ckt1 and Ckt2 for Duplex
chillers
On/Off
Auto
On
Oil Pump Manual Override Time Remaining
Oil Differential Pressure
Oil Pump Discharge Pressure
Oil Tank Pressure
Clear Restart Inhibit
Note: Ckt1 and Ckt2 for Duplex
chillers
XX:XX min:sec
Clear
Motor Temperature
Motor Winding Temp #1
Motor Winding Temp #2
Motor Winding Temp #3
MTC Switch
Motor Coolant Temperature
Purge Exhaust Circuit Test
Note: Ckt1 and Ckt2 for Duplex
chillers
Auto/On
Enable
Disable
Purge Rfgt Cprsr Suction Temp
Purge Liquid Temp
Purge Regen Cycle
Note: Ckt1 and Ckt2 for Duplex
chillers
On/Off
Auto
On
Carbon Tank Temp
Front Panel Lockout
Note: Duplex chillers only; for Ckt1
and Ckt2.
Locked Out
Not Locked Out
Chiller Top Level Mode
Top Level Operating Mode Ckt1
Top Level Operating Mode Ckt2
Head Pressure Control Override
Cond Entering
Water Temp
XXX.X °F/C
Cond Leaving Water Temp Cond Rfgt Pressure