Appendix
104 CNT-SVX05B-EN
Pre-cool Pre-cool Cool Fan enabled
Heating disabled
Cooling enabled
Damper ventilation disabled
Economizer enabled
Off Off Auto Fan disabled
Heating disabled
Cooling disabled
Damper disabled
Test Determined by controller Determined by controller Fan enabled
Heating enabled
Cooling enabled
Damper enabled
Fan only Fan only Auto Fan enabled
Heating disabled
Cooling disabled
Damper disabled
Maximum flow heating Maximum flow heating Maximum flow heating Fan enabled
Heating enabled
Cooling disabled
Damper enabled
1 Heating capacity can be used to control the discharge air temperature to the discharge air cooling setpoint.
Table 72. Discharge air temperature control operation based on effective heat/cool output (continued)