DynaView Interface
RLC-SVU05A-E418
* Mode text strings in parenthesis for TechView display only - available space for DynaView text strings is limited.
Circuit Level Mode
Top Level Mode Description
Shutting Down
The circuit is preparing to de-energize the compressor.
Preparing Shutdown
Sub Modes
Description
Operational Pumpdown
The circuit is in the process shutting down by performing an operational pumpdown just prior to
stopping the last running compressor. The EXV is commanded closed. Pumpdown will terminate
when both the liquid level and the evap pressure are low (below specific criteria) or after a specific
time has expired.
Compressor Unloading: MIN:SEC
The compressor is in its run unload time. The number of seconds remaining in run unload is shown in
the submode. The run unload time must expire before the compressor will shut down.
Circuit Level Mode
Top Level Mode Description
Misc.
These sub modes may be displayed in most of the top level circuit modes
Misc. Sub Modes Description
Service Pumpdown The circuit is currently performing a service pumpdown.
Restart Time Inhibit: MIN:SEC If there is accumulated Restart Inhibit Time, it must expire before a compressor is allowed to start.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer CH530 and is the answer not in the manual?

Trane Tracer CH530 Specifications

General IconGeneral
SeriesTracer CH530
Input Voltage24 VAC
Communication ProtocolsBACnet, LonWorks
CompatibilityTrane
Product TypeChiller controller
MemoryFlash memory for program storage
DimensionsVaries depending on the specific model and enclosure. (Example: Approximately 250mm x 200mm x 100mm)
WeightVaries by configuration

Related product manuals