Main Processor Diagnostics
33RLC-SVU05A-E4
Diagnostic Name
Affects
Ta r g e t
Severity Persistence
Active Modes
[Inactive Modes]
Criteria Reset Level
MP: Reset Has
Occurred
None Info
NonLatch
All The main processor has successfully come out of a
reset and built its application. A reset may have been
due to a power up, installing new software or
configuration. This diagnostic is immediately and
automatically cleared and thus can only be seen in the
Historic Diagnostic List in TechView
Remote
Unexpected Starter
Shutdown
Circuit Normal
NonLatch
All Cprsr Running
modes, Starting,
Running and Preparing
to Shutdown
The Starter module status reported back that it is
stopped when the MP thinks it should be running and
no Starter diagnostic exist. This diagnostic will be
logged in the active buffer and then automatically
cleared. This diagnostic could be caused by intermittent
communication problems from the Starter to the MP, or
due to misbinding.
NA
High Motor Winding
Temperature -
Compressor 1A
Circuit Immediate
Latch
All The respective compressor's motor winding thermostat
is detected to be open
Local
High Motor Winding
Temperature -
Compressor 2A
Circuit Immediate
Latch
All The respective compressor's motor winding thermostat
is detected to be open
Local
Low Evaporator
Refrigerant
Temperature -
Circuit 1
Circuit Immediate
Latch
All Ckt Running
Modes
The inferred Saturated Evap Refrigerant Temperature
(calculated from suction pressure transducer dropped
below the Low Refrigerant Temperature Cutout Setpoint
for 1125°F-sec (25°F-sec max rate) while the circuit was
running. The minimum LRTC setpoint is -5°F (18.7 Psia)
the point at which oil separates from the refrigerant.
During the time that the trip integral is non zero, the
unload solenoid(s) of the running compressors on the
circuit, shall be energized continuously and the load
solenoid shall be off. Normal load/unload operation will
be resumed if the trip integral decays to zero by temps
above the cutout setpoint. The integral is held
nonvolatily though power down, is continuously
calculated, and can decay during the circuit's off cycle as
conditions warrant.
Remote
Low Evaporator
Refrigerant
Temperature -
Circuit 2
Circuit Immediate
Latch
All Ckt Running
Modes
The inferred Saturated Evap Refrigerant Temperature
(calculated from suction pressure transducer dropped
below the Low Refrigerant Temperature Cutout Setpoint
for 1125°F-sec (25°F-sec max rate) while the circuit was
running. The minimum LRTC setpoint is -5°F (18.7 Psia)
the point at which oil separates from the refrigerant.
During the time that the trip integral is non zero, the
unload solenoid(s) of the running compressors on the
circuit, shall be energized continuously and the load
solenoid shall be off. Normal load/unload operation will
be resumed if the trip integral decays to zero by temps
above the cutout setpoint. The integral is held
nonvolatily though power down, is continuously
calculated, and can decay during the circuit's off cycle as
conditions warrant.
Remote