Main Processor Diagnostics
35RLC-SVU05A-E4
Diagnostic Name
Affects
Ta r g e t
Severity Persistence
Active Modes
[Inactive Modes]
Criteria Reset Level
High Differential
Refrigerant
Pressure - Circuit 2
Circuit Normal
Latch
Cprsr Energized High Vi Cprsr: The differential pressure for the
respective circuit was above 275 Psid (1890 kPa) for 2
consecutive samples or more than 10 seconds.
Low Vi Cprsr: The system differential pressure was
above 188 Psid (1296.4 kPa) - for 2 consecutive
samples or more than 10 seconds.
Remote
High Refrigerant
Pressure Ratio -
Circuit 1
Circuit Immediate
Latch
Service Pumpdown
Only
The pressure ratio for the respective circuit exceeded
5.61 for 1 contiguous minute while in service
pumpdown. This pressure ratio is a fundamental
limitation of the compressor. The pressure ratio is
defined as Pcond (abs)/Pevap(abs).
Remote
High Refrigerant
Pressure Ratio -
Circuit 2
Circuit Immediate
Latch
Service Pumpdown
Only
The pressure ratio for the respective circuit exceeded
5.61 for 1 contiguous minute while in service
pumpdown. This pressure ratio is a fundamental
limitation of the compressor. The pressure ratio is
defined as Pcond (abs)/Pevap(abs).
Remote
High Discharge
Temperature -
Compressor 1A
Circuit Immediate
Latch
All
[compressor run
unload or compressor
not running]
The compressor discharge temperature exceeded 200°F
(without oil cooler) or 230ºF (with oil cooler). This
diagnostic will be suppressed during Run-Unload or after
the compressor has stopped. Note: As part of the
Compressor High Temperature Limit Mode (aka
Minimum Capacity Limit), the compressor shall be
forced loaded as the filtered discharge temperature
reaches 190ºF(without oil coolers), or 220ºF (with oil
coolers).
Remote
High Discharge
Temperature -
Compressor 2A
Circuit Immediate
Latch
All
[compressor run
unload or compressor
not running]
The compressor discharge temperature exceeded 200°F
(without oil cooler) or 230ºF (with oil cooler). This
diagnostic will be suppressed during Run-Unload or after
the compressor has stopped. Note: As part of the
Compressor High Temperature Limit Mode (aka
Minimum Capacity Limit), the compressor shall be
forced loaded as the filtered discharge temperature
reaches 190ºF(without oil coolers), or 220ºF (with oil
coolers).
Remote
Low Discharge
Superheat -
Circuit 1
Circuit Normal Latch Any Running Mode
While Running Normally, the Discharge Superheat was
less than 12 degrees F +- 1F for more than 6500 degree
F seconds.. At circuit startup the Discharge Superheat
will be ignored for 5 minutes.
Remote
Low Discharge
Superheat -
Circuit 2
Circuit Normal Latch Any Running Mode
While Running Normally, the Discharge Superheat was
less than 12 degrees F +- 1F for more than 6500 degree
F seconds.. At circuit startup the Discharge Superheat
will be ignored for 5 minutes.
Remote
Discharge
Temperature
Sensor -
Compressor 1A
Circuit Immediate Latch All Bad Sensor or LLID Remote
Discharge
Temperature
Sensor -
Compressor 2A
Circuit Immediate Latch All Bad Sensor or LLID Remote
Evaporator Liquid
Level Sensor -
Circuit 1
Circuit Normal Latch All Bad Sensor or LLID Remote
Evaporator Liquid
Level Sensor -
Circuit 2
Circuit Normal
Latch
All Bad Sensor or LLID Remote