Procedure Measurement
Expected Value
Step 1
Measure AC voltage across the resistive
termination.
Vac 0.0 V
AC voltage will affect further
measurement.
Step 2
Measure DC voltage across the resistive
termination.
Vdc 0.0 V
DC voltage will affect further
measurement.
Step 3
Measure the resistance across the resistive
termination.
contact open = infinity (∞)
contact closed = shorted (0 Ω)