BAS-SVP042A-EN
Object and Diagnostic Data Points
For quick reference, the following tables are listed and sorted two different ways. Table 2, p. 18
through Table 8, p. 29 are listed by input/output type and sorted by object name. Table 9, p. 32 is
sorted by Object Name.
NNoottee:: Not all points are available to the user. The available data points are defined and
dependent on the type of equipment and options.
Table 2. Analog Inputs
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
AI1
Space Temperature
Local
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with Space
Temperature Option.
Local Space Temperature Sensor. Read Only
AI12
Duct Static Pressure
Local
Pressure
in(H2O)
-0.25 to 5.2 in
(H2O)
All Units Local Duct Static Pressure Sensor.
Read Only
AI32
Return Air
Temperature Local
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
All Units
Local Return Air Tempreature Sensor Read Only
AI46
Condenser Water
Entering Temperature
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Water Cooled
Condenser Units
Only
Local Condenser Water Entering
Temperature Sensor
Read Only
AI47
Condenser Water
Leaving Temperature
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Water Cooled
Condenser Units
Only
Local condenser Water Leaving
Temperature Sensor
Read Only
AI48
Condenser Tee
Strainer High Pressure
Pressure
(PSI)
-500 to 550 PSI
Water Cooled
Condenser Units
Only
Local Condenser Tee Strainger High
Pressure Sensor
Read Only
AI49
Condenser Tee
Strainer Low Pressure
Pressure
(PSI)
-500 to 550 PSI
Water Cooled
Condenser Units
Only
Local Condenser Tee Strainger Low
Pressure Sensor
Read Only
AI58
Air Filter Differential
Pressure
Pressure
in(H2O)
-10 to 10 in
(H2O)
All Units
Local Air Filter Differentil Pressure
Sensor
Read Only
AI93
Compressor 1
Discharge Pressure
Sensor
Pressure
(PSI)
0 to 750 PSI
Units with at least 1
Compressor
Local Compressor Refrigerant
Discharge (High) Pressure Sensor
Read Only
AI94
Compressor 1 Suction
Pressure Sensor
Pressure
(PSI)
0 to 750 PSI
Units with at least 1
Compressor
Local Compressor Refrigerant Suction
(Low) Pressure Sensor
Read Only
AI95
Compressor 1 Suction
Temperature
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with at least 1
Compressor
Local Compressor Refrigerant Suction
(Low) Temperature Sensor
Read Only
AI96
Compressor 2
Discharge Pressure
Sensor
Pressure
(PSI)
0 to 750 PSI
Units with at least 2
Compressors
Local Compressor Refrigerant
Discharge (High) Pressure Sensor
Read Only
AI97
Compressor 2 Suction
Pressure Sensor
Pressure
(PSI)
0 to 750 PSI
Units with at least 2
Compressors
Local Compressor Refrigerant Suction
(Low) Pressure Sensor
Read Only
AI98
Compressor 2 Suction
Temperature
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with at least 2
Compressors
Local Compressor Refrigerant Suction
(Low) Temperature Sensor
Read Only
AI99
Compressor 3
Discharge Pressure
Sensor
Pressure
(PSI)
0 to 750 PSI
Units with at least 3
Compressors
Local Compressor Refrigerant
Discharge (High) Pressure Sensor
Read Only
AI100
Compressor 3 Suction
Pressure Sensor
Pressure
(PSI)
0 to 750 PSI
Units with at least 3
Compressors
Local Compressor Refrigerant Suction
(Low) Pressure Sensor
Read Only
AI101
Compressor 3 Suction
Temperature
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with at least 3
Compressors
Local Compressor Refrigerant Suction
(Low) Temperature Sensor
Read Only
AI102
Compressor 4
Discharge Pressure
Sensor
Pressure
(PSI)
0 to 750 PSI
Units with at least 4
Compressors
Local Compressor Refrigerant
Discharge (High) Pressure Sensor
Read Only
AI103
Compressor 4 Suction
Pressure Sensor
Pressure
(PSI)
0 to 750 PSI
Units with at least 4
Compressors
Local Compressor Refrigerant Suction
(Low) Pressure Sensor
Read Only
AI104
Compressor 4 Suction
Temperature
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with at least 4
Compressors
Local Compressor Refrigerant Suction
(Low) Temperature Sensor
Read Only
Table 3. Analog Outputs
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
AO81
Compressor 1
Condenser Regulating
Valve
Percent
0% to 100%
Open
Unit that Circuit 1
has a Water
Regulating Valve
installed
Analog Control that regulates water
throught the water cooled condenser
of the compressor
Read Only
AO82
Compressor 2
Condenser Regulating
Valve
Percent
0% to 100%
Open
Unit that Circuit 2
has a Water
Regulating Valve
installed
Analog Control that regulates water
throught the water cooled condenser
of the compressor
Read Only