EasyManua.ls Logo

Trane Tracer UC600 - Installation; Mounting and Removing the UC600 Controller

Trane Tracer UC600
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BAS-SVP042A-EN
13
MS/TP MAC Address
Each device on a BACnet MS/TP network must be assigned a unique physical address. This is
referred to as the Media Access Control (MAC) address. The BACnet Standard defines the valid
address range of a MS/TP master device as zero (0) to 127. All Trane devices are master devices.
When a Tracer SC device is present on the MS/TP network, Trane restricts the use of the zero (0)
MAC address. This address is assigned to the Tracer SC and cannot be changed. All other
BACnet MS/TP master devices, including the UC600, must have a MAC addresses within the
range of 1 to 127. The three (3) rotary switches on the front of the UC600 device are used to set
the MAC address.
Failure to assign a unique address to each device on the network will cause network
communication failure.