Table 9. All Object Types Sorted by Object Name
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
AV133
Active CoolCoil Control
Sensor
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
All Units
Active Temperature used for
controlling the cooling calculation
Read Only
BV76
Active CoolCoil Control
Sensor Failed
None None All Units
Open = Normal
Closed = Failure
Non latching Diagnostic, clears
automatically
Read Only
AV134
Active CoolCoil Control
Setpoint
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
All Units
Active Setpoint used for controlling
the cooling calculation
Read Only
AI58
Air Filter Differential
Pressure
Pressure
in(H2O)
-10 to 10 in
(H2O)
All Units
Local Air Filter Differentil Pressure
Sensor
Read Only
BV36 Alarm Reset None None All Units
Open = Normal
Closed = Reset
Read Only
AV162
Circuit 1 Compressor
Speed
Percent -150% to 150%
Units with variable
speed compressor
(s)
Speed Status for the variable speed
compressor.
Read Only
AV300
Compressor 1
Calculated Diff
Refrigerant Pressure
PSI
-500 psi to 500
psi
Units with 1
Compressor
Calculated Differential Pressure
between the Discharge and Suction
Pressure Sensors
Read Only
AV301
Compressor 1
Calculated Max Speed
(Percent)
Percent -150% to 150%
Units with 1
Compressor
Calculated Maximum Speed in RPM of
the Variable speed Compressor
Read Only
AV302
Compressor 1
Calculated Saturated
Discharge Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 1
Compressor
Calculated Saturated Discharge
Temperature calcualted by the
refrigerant temp and pressure.
Read Only
AV303
Compressor 1
Calculated Saturated
Suction Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 1
Compressor
Calculated Suction Temperature by
pressure to temperature conversion.
Read Only
AV304
Compressor 1
Calculated Speed
(RPM)
None 0 - 15000 RPM
Units with 1
Compressor
Calculation of the current speed of the
variable speed compressor, based on
Min and Max speed setpoints.
Read Only
BV190
Compressor 1
Calculated Status
None None
Units with 1
Compressor
Open = Off
Closed = On
Read Only
AV305
Compressor 1
Calculated Superheat
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 1
Compressor
Calculated Superheat of the Suction
line by Temperautre and pressure
sensors.
Read Only
BV191
Compressor 1 Call
None None
Units with 1
Compressor
Open = Stop
Closed = Run
Read Only
BO11
Compressor 1
Command
None None
Units with at least 1
Compressor
Normally Open Contacts Used Only
Open = Stop Closed = Run
Normally Closed Contacts not used
Read Only
BV193
Compressor 1 Cond
Purge Status
None None
Units with 1
Compressor
Open = Inactive
Closed = Purge Active
Read Only
BV194
Compressor 1 Cond
Valve Open
None None
Units with 1
Compressor
Open = Closed
Closed = Open
Read Only
AO81
Compressor 1
Condenser Regulating
Valve
Percent
0% to 100%
Open
Unit that Circuit 1
has a Water
Regulating Valve
installed
Analog Control that regulates water
throught the water cooled condenser
of the compressor
Read Only
AI93
Compressor 1
Discharge Pressure
Sensor
Pressure
(PSI)
0 to 750 PSI
Units with at least 1
Compressor
Local Compressor Refrigerant
Discharge (High) Pressure Sensor
Read Only
AV306
Compressor 1
Estimated Cond
Approach Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 1
Compressor with
Cond Reg Valve
Calculated Condenser approach
temperature based off Refrigerant PT
Conversion and water temperature.
Read Only
AV307
Compressor 1
Estimated Evap
Approach Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 1
Compressor
Calculated approach temperuatre of
the Evaporator refrigerant temprature
and the air temperature.
Read Only
BO109
Compressor 1 E-Stop
Shutdown Command
None None
Unit where
compressor 1 is a
VFD Compressor
Normally Open Contacts Used Only
Open = Normal Closed = Emergency
Stop
Normally Closed Contacts not used
Read Only
BV195
Compressor 1 Failure
Reset
None None
Units with 1
Compressor
Open = Normal
Closed = Reset
Read Only
BI90
Compressor 1 High
Pressure Cutout
None None
Units with at least 1
Compressor
Normally Closed Input
Open = Alarm
Closed = Normal
Read Only
BV29
Compressor 1 Lockout
BAS
None None
Units with at least 1
Compressor
Open = Available
Closed = Locked Out
Read Only