Table 9. All Object Types Sorted by Object Name (continued)
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
AV308
Compressor 1 Max
Cond Valve Setpoint
Percent -150% to 150%
Units with 1
Compressor with
Cond Reg Valve
Maximum Valve position for the
condenser regulating valve.
Read Only
AV309
Compressor 1 Max
Speed (RPM)
None
5500 -15000
RPM
Units with 1
Compressor
Maximum Speed for the installed
Compressor (Set at Factory)
Read Only
AV310
Compressor 1 Max
Speed Setpt (RPM)
None
5500 -15000
RPM
Units with 1
Compressor
Maximum Speed Setpoint for the
installed compressor. (May not be the
compressor maximum and set at
Factory)
Read Only
AV311
Compressor 1 Min
Cond Valve Setpoint
Percent -150% to 150%
Units with 1
Compressor with
Cond Reg Valve
Maximum Valve position for the
condenser regulating valve.
Read Only
AV312
Compressor 1 Min
Speed (RPM)
None
1100 -15000
RPM
Units with 1
Compressor
Maximum Speed for the installed
Compressor. (Set at Factory)
Read Only
AV313
Compressor 1 Min
Speed Setpt (RPM)
None 1200 - 4000 RPM
Units with 1
Compressor
Maximum Speed Setpoint for the
installed compressor. (May not be the
compressor maximum and set at
factory)
Read Only
MV70
Compressor 1 Mode
None None
Units with at least 1
Compressor
[1, Off]
[2, Starting]
[3, Running]
[4, Diag: Safety Circuit Alarm]
[5, Diag: Low Superheat]
[6, Diag: Suction Press Sensor Failure]
[7, Diag: Suction Temp Sensor
Failure]
[8, Diag: Frostat Aarm]
[9, Diag: Discharge Press Sensor
Failure]
[10, Diag: High Pressure Cutout
Alarm]
[11, VFD Fault]
[12, Diag: High Superheat]
[13, Warn: Cond Limit Active]
[14, Comp Locked Out]
[15, Warn: Frostat Limit Active]
_x000D_
Read Only
BV196
Compressor 1 Run
Hour Reset
None None
Units with 1
Compressor
Open = Normal
Closed = Reset
Read Only
AV314
Compressor 1 Run
Hours
None
0 -
9999999827968
Units with 1
Compressor
Totalized run hours of the compressor
from the last run hour reset or
program change.
Read Only
BV197
Compressor 1 Safety
Lockout
None None
Units with 1
Compressor
Open = Inactive
Closed = Lockout Active
Read Only
BI114
Compressor 1 Status
None None
Unit where
compressor 1 is a
VFD Compressor
Normally Open Input
Open = Off
Closed = On
Read Only
AI94
Compressor 1 Suction
Pressure Sensor
Pressure
(PSI)
0 to 750 PSI
Units with at least 1
Compressor
Local Compressor Refrigerant Suction
(Low) Pressure Sensor
Read Only
AI95
Compressor 1 Suction
Temperature
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with at least 1
Compressor
Local Compressor Refrigerant Suction
(Low) Temperature Sensor
Read Only
AO90
Compressor 1 Variable
Speed Command
Percent
0% to 100%
Speed
Unit where
compressor 1 is a
VFD Compressor
Analog signal that controls the
compressor speed
Read Only
BO108
Compressor 1 VFD
Alarm Reset
None None
Unit where
compressor 1 is a
VFD Compressor
Normally Open Contacts Used Only
Open = Normal Closed = Reset
Normally Closed Contacts not used
Read Only
BI98
Compressor 1 VFD
Fault
None None
Units with at least 1
Compressor
Normally Closed Input
Open = Alarm
Closed = Normal
Read Only
AV319
Compressor 2
Calculated Diff
Refrigerant Pressure
PSI
-500 psi to 500
psi
Units with 2
Compressor
Calculated Differential Pressure
between the Discharge and Suction
Pressure Sensors
Read Only
AV320
Compressor 2
Calculated Saturated
Discharge Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 2
Compressor
Calculated Saturated Discharge
Temperature calcualted by the
refrigerant temp and pressure.
Read Only
AV321
Compressor 2
Calculated Saturated
Suction Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 2
Compressor
Calculated Suction Temperature by
pressure to temperature conversion.
Read Only