34
BAS-SVP042A-EN
Table 9. All Object Types Sorted by Object Name (continued)
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
BV200
Compressor 2
Calculated Status
None None
Units with 1
Compressor
Open = Off
Closed = On
Read Only
AV322
Compressor 2
Calculated Superheat
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 2
Compressor
Calculated Superheat of the Suction
line by Temperautre and pressure
sensors.
Read Only
BV201
Compressor 2 Call
None None
Units with 1
Compressor
Open = Stop
Closed = Run
Read Only
BO12
Compressor 2
Command
None None
Units with at least 2
Compressors
Normally Open Contacts Used Only
Open = Stop Closed = Run
Normally Closed Contacts not used
Read Only
BV203
Compressor 2 Cond
Purge Status
None None
Units with 1
Compressor
Open = Inactive
Closed = Purge Active
Read Only
BV204
Compressor 2 Cond
Valve Open
None None
Units with 1
Compressor
Open = Closed
Closed = Open
Read Only
AO82
Compressor 2
Condenser Regulating
Valve
Percent
0% to 100%
Open
Unit that Circuit 2
has a Water
Regulating Valve
installed
Analog Control that regulates water
throught the water cooled condenser
of the compressor
Read Only
AI96
Compressor 2
Discharge Pressure
Sensor
Pressure
(PSI)
0 to 750 PSI
Units with at least 2
Compressors
Local Compressor Refrigerant
Discharge (High) Pressure Sensor
Read Only
AV323
Compressor 2
Estimated Cond
Approach Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 2
Compressor with
Cond Reg Valve
Calculated Condenser approach
temperature based off Refrigerant PT
Conversion and water temperature.
Read Only
AV324
Compressor 2
Estimated Evap
Approach Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 2
Compressor
Calculated approach temperuatre of
the Evaporator refrigerant temprature
and the air temperature.
Read Only
BV205
Compressor 2 Failure
Reset
None None
Units with 1
Compressor
Open = Normal
Closed = Reset
Read Only
BI91
Compressor 2 High
Pressure Cutout
None None
Units with at least 2
Compressors
Normally Closed Input
Open = Alarm
Closed = Normal
Read Only
BV30
Compressor 2 Lockout
BAS
None None
Units with at least 2
Compressors
Open = Available
Closed = Locked Out
Read Only
AV325
Compressor 2 Max
Cond Valve Setpoint
Percent -150% to 150%
Units with 2
Compressor with
Cond Reg Valve
Maximum Valve position for the
condenser regulating valve.
Read Only
AV326
Compressor 2 Min
Cond Valve Setpoint
Percent -150% to 150%
Units with 2
Compressor with
Cond Reg Valve
Maximum Valve position for the
condenser regulating valve.
Read Only
MV71
Compressor 2 Mode
None None
Units with at least 2
Compressors
[1, Off]
[2, Starting]
[3, Running]
[4, Diag: Safety Circuit Alarm]
[5, Diag: Low Superheat]
[6, Diag: Suction Press Sensor Failure]
[7, Diag: Suction Temp Sensor
Failure]
[8, Diag: Frostat Aarm]
[9, Diag: Discharge Press Sensor
Failure]
[10, Diag: High Pressure Cutout
Alarm]
[11, VFD Fault]
[12, Diag: High Superheat]
[13, Warn: High Disc Press]
[14, Comp Locked Out]
[15, Warn: Frostat Warning]
Read Only
BV206
Compressor 2 Run
Hour Reset
None None
Units with 1
Compressor
Open = Normal
Closed = Reset
Read Only
AV327
Compressor 2 Run
Hours
None
0 -
9999999827968
Units with 2
Compressor
Totalized run hours of the compressor
from the last run hour reset or
program change.
Read Only
BI107
Compressor 2 Safety
Circuit Status
None None
Units with at least 2
Compressors
Normally Open Input
Open = Circuit Open
Closed = Circuit Closed (Completed)
Read Only
BV207
Compressor 2 Safety
Lockout
None None
Units with 1
Compressor
Open = Inactive
Closed = Lockout Active
Read Only
AV328
Compressor 2
Sequence Number
None 0 - 5
Units with 2
Compressor
Sequence Number to indicate what
sequence the compressor will start in.
Read Only
OObbjjeecctt aanndd DDiiaaggnnoossttiicc DDaattaa PPooiinnttss