BAS-SVP042A-EN
35
Table 9. All Object Types Sorted by Object Name (continued)
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
AI97
Compressor 2 Suction
Pressure Sensor
Pressure
(PSI)
0 to 750 PSI
Units with at least 2
Compressors
Local Compressor Refrigerant Suction
(Low) Pressure Sensor
Read Only
AI98
Compressor 2 Suction
Temperature
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with at least 2
Compressors
Local Compressor Refrigerant Suction
(Low) Temperature Sensor
Read Only
AV333
Compressor 3
Calculated Diff
Refrigerant Pressure
PSI
-500 psi to 500
psi
Units with 3
Compressor
Calculated Differential Pressure
between the Discharge and Suction
Pressure Sensors
Read Only
AV334
Compressor 3
Calculated Saturated
Discharge Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 3
Compressor
Calculated Saturated Discharge
Temperature calcualted by the
refrigerant temp and pressure.
Read Only
AV335
Compressor 3
Calculated Saturated
Suction Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 3
Compressor
Calculated Suction Temperature by
pressure to temperature conversion.
Read Only
BV210
Compressor 3
Calculated Status
None None
Units with 1
Compressor
Open = Off
Closed = On
Read Only
AV336
Compressor 3
Calculated Superheat
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 3
Compressor
Calculated Superheat of the Suction
line by Temperautre and pressure
sensors.
Read Only
BV211
Compressor 3 Call
None None
Units with 1
Compressor
Open = Stop
Closed = Run
Read Only
BO13
Compressor 3
Command
None None
Units with at least 3
Compressors
Normally Open Contacts Used Only
Open = Stop Closed = Run
Normally Closed Contacts not used
Read Only
BV213
Compressor 3 Cond
Purge Status
None None
Units with 1
Compressor
Open = Inactive
Closed = Purge Active
Read Only
BV214
Compressor 3 Cond
Valve Open
None None
Units with 1
Compressor
Open = Closed
Closed = Open
Read Only
AO83
Compressor 3
Condenser Regulating
Valve
Percent
0% to 100%
Open
Unit that Circuit 3
has a Water
Regulating Valve
installed
Analog Control that regulates water
throught the water cooled condenser
of the compressor
Read Only
AI99
Compressor 3
Discharge Pressure
Sensor
Pressure
(PSI)
0 to 750 PSI
Units with at least 3
Compressors
Local Compressor Refrigerant
Discharge (High) Pressure Sensor
Read Only
AV337
Compressor 3
Estimated Cond
Approach Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 3
Compressor with
Cond Reg Valve
Calculated Condenser approach
temperature based off Refrigerant PT
Conversion and water temperature.
Read Only
AV338
Compressor 3
Estimated Evap
Approach Temp
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with 3
Compressor
Calculated approach temperuatre of
the Evaporator refrigerant temprature
and the air temperature.
Read Only
BV215
Compressor 3 Failure
Reset
None None
Units with 1
Compressor
Open = Normal
Closed = Reset
Read Only
BI92
Compressor 3 High
Pressure Cutout
None None
Units with at least 3
Compressors
Normally Closed Input
Open = Alarm
Closed = Normal
Read Only
BV31
Compressor 3 Lockout
BAS
None None
Units with at least 3
Compressors
Open = Available
Closed = Locked Out
Read Only
AV339
Compressor 3 Max
Cond Valve Setpoint
Percent -150% to 150%
Units with 3
Compressor with
Cond Reg Valve
Maximum Valve position for the
condenser regulating valve.
Read Only
AV340
Compressor 3 Min
Cond Valve Setpoint
Percent -150% to 150%
Units with 3
Compressor with
Cond Reg Valve
Maximum Valve position for the
condenser regulating valve.
Writeable
OObbjjeecctt aanndd DDiiaaggnnoossttiicc DDaattaa PPooiinnttss