28
BAS-SVP042A-EN
Table 7. Binary Values (continued)
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
BV326
Fixed Speed
Compressor Rotate
BAS
None None
Units with more than
2 Compressors
Open = Normal
Closed = Rotate
Writeable
BV327
Fixed Speed
Compressor Rotate
Schedule=BAS/Local
None None
Units with more than
2 Compressors
Open = BAS
Closed = Local
Writeable
BV329
Local Auto Stop
None None All Units
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Writeable
BV330
Supply Fan 1
Calculated Status
None None
Units with at least 1
Supply Fan
Open = Off
Closed = On
Read Only
BV331
Supply Fan 1 Failure
None None
Units with at least 1
Supply Fan
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Read Only
BV332
Supply Fan 1 Lockout
BAS
None None
Units with at least 1
Supply Fan
Open = Available
Closed = Locked Out
Writeable
BV335
Supply Fan 2
Calculated Status
None None
Units with at least 2
Supply Fan
Open = Off
Closed = On
Read Only
BV336
Supply Fan 2 Failure
None None
Units with at least 2
Supply Fan
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Read Only
BV337
Supply Fan 2 Lockout
BAS
None None
Units with at least 2
Supply Fan
Open = Available
Closed = Locked Out
Writeable
BV340
Supply Fan 3
Calculated Status
None None
Units with at least 3
Supply Fan
Open = Off
Closed = On
Read Only
BV341
Supply Fan 3 Failure
None None
Units with at least 3
Supply Fan
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Read Only
BV342
Supply Fan 3 Lockout
BAS
None None
Units with at least 3
Supply Fan
Open = Available
Closed = Locked Out
Writeable
BV345
Supply Fan 4
Calculated Status
None None
Units with at least 4
Supply Fan
Open = Off
Closed = On
Read Only
BV346
Supply Fan 4 Failure
None None
Units with at least 4
Supply Fan
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Read Only
BV347
Supply Fan 4 Lockout
BAS
None None
Units with at least 4
Supply Fan
Open = Available
Closed = Locked Out
Writeable
BV350
Supply Fan 5
Calculated Status
None None
Units with at least 5
Supply Fan
Open = Off
Closed = On
Read Only
BV351
Supply Fan 5 Failure
None None
Units with at least 5
Supply Fan
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Read Only
BV352
Supply Fan 5 Lockout
BAS
None None
Units with at least 5
Supply Fan
Open = Available
Closed = Locked Out
Writeable
BV355
Supply Fan 6
Calculated Status
None None
Units with at least 6
Supply Fan
Open = Off
Closed = On
Read Only
BV356
Supply Fan 6 Failure
None None
Units with at least 6
Supply Fan
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Supply Fan Failure Reset or Power
Cycle.
Read Only
BV357
Supply Fan 6 Lockout
BAS
None None
Units with at least 6
Supply Fan
Open = Available
Closed = Locked Out
Writeable
BV360
Supply Fan Calculated
Status
None None All Units
Open = Off
Closed = Running
Read Only
BV365
Warning: Compressor
1 Cond Limit Status
None None
Units with at least 1
Compressor
Open = Normal Capacity
Closed = Limited Capacity
Read Only
BV366
Warning: Compressor
1 Frostat Limit Status
None None
Units with at least 1
Compressor
Open = Normal
Closed = Warning Active
Read Only
BV370
Warning: Compressor
2 Frostat Warning
None None
Units with at least 2
Compressor
Open = Normal
Closed = Warning Active
Read Only
OObbjjeecctt aanndd DDiiaaggnnoossttiicc DDaattaa PPooiinnttss