Table 9. All Object Types Sorted by Object Name (continued)
Object
Identifi-
er
Object Name
Units of
Measure
Minimum
Maximum
When the Object
Exists
Description
Read/
Write
BV225
Compressor 4 Failure
Reset
None None
Units with 1
Compressor
Open = Normal
Closed = Reset
Read Only
BI93
Compressor 4 High
Pressure Cutout
None None
Units with at least 4
Compressors
Normally Closed Input
Open = Alarm
Closed = Normal
Read Only
BV32
Compressor 4 Lockout
BAS
None None
Units with at least 4
Compressors
Open = Available
Closed = Locked Out
Read Only
AV353
Compressor 4 Max
Cond Valve Setpoint
Percent -150% to 150%
Units with 4
Compressor with
Cond Reg Valve
Maximum Valve position for the
condenser regulating valve.
Writeable
AV354
Compressor 4 Min
Cond Valve Setpoint
Percent -150% to 150%
Units with 4
Compressor with
Cond Reg Valve
Maximum Valve position for the
condenser regulating valve.
Read Only
MV73
Compressor 4 Mode
None None
Units with at least 4
Compressors
[1, Off]
[2, Starting]
[3, Running]
[4, Diag: Safety Circuit Alarm]
[5, Diag: Low Superheat]
[6, Diag: Suction Press Sensor Failure]
[7, Diag: Suction Temp Sensor
Failure]
[8, Diag: Frostat Aarm]
[9, Diag: Discharge Press Sensor
Failure]
[10, Diag: High Pressure Cutout
Alarm]
[11, VFD Fault]
[12, Diag: High Superheat]
[13, Warn: High Disc Press]
[14, Comp Locked Out]
[15, Warn: Frostat Warning]
Writeable
BV226
Compressor 4 Run
Hour Reset
None None
Units with 1
Compressor
Open = Normal
Closed = Reset
Read Only
AV355
Compressor 4 Run
Hours
None
0 -
9999999827968
Units with 4
Compressor
Totalized run hours of the compressor
from the last run hour reset or
program change.
Read Only
BI109
Compressor 4 Safety
Circuit Status
None None
Units with at least 4
Compressors
Normally Open Input
Open = Circuit Open
Closed = Circuit Closed (Completed)
Read Only
BV227
Compressor 4 Safety
Lockout
None None
Units with 1
Compressor
Open = Inactive
Closed = Lockout Active
Read Only
AV356
Compressor 4
Sequence Number
None 0 - 5
Units with 4
Compressor
Sequence Number to indicate what
sequence the compressor will start in.
Read Only
AI103
Compressor 4 Suction
Pressure Sensor
Pressure
(PSI)
0 to 750 PSI
Units with at least 4
Compressors
Local Compressor Refrigerant Suction
(Low) Pressure Sensor
Read Only
AI104
Compressor 4 Suction
Temperature
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
Units with at least 4
Compressors
Local Compressor Refrigerant Suction
(Low) Temperature Sensor
Read Only
BV250
Compressor Cond
Valve Installed
None None All Units
Open = Not Installed
Closed = Installed
Read Only
AV176
Compressor Error
Deadband
Temperature
(°C or °F)
-50°C (-58°F) to
236°C (482°F)
All Units
Deadband Compressor calculation
uses for speed calculation
Read Only
AV173
Compressor P Gain
None 0.5 to 25 All Units
P Gain for the PID Cooling Calculation Read Only
AV174
Compressor Speed P
Gain
None 0.5 to 25 All Units
P Gain for the PID Cooling Calculation
Writeable
AV361
Compressors Available
None -1000 to 1000 All Units
Number of Compressor which are
available to run.
Read Only
AV363
Condenser Control
Percent of Design
Percent 50 % to 100 %
Water Cooled
Condenser Units
Only
sets the percentage of the Control
Pressure Setpoint that will be used to
control the Discharge Pressure on the
unit
Writeable
AV366
Condenser Control
Pressure Setpoint
PSI
-500 psi to 500
psi
Water Cooled
Condenser Units
Only
Calculated Condenser Control
Pressure Setpoint based on the
Percentage of Design and the Max
Pressure
Read Only
AV364
Condenser Design
Max Pressure
PSI
-500 psi to 500
psi
Water Cooled
Condenser Units
Only
Condenser Max Design Pressure set by
the Factory.
Read Only