Table 10. Alarm Objects (continued)
Object Identifier Object Name Description
Notification Class
BV262
Diagnostic:
Compressor 1 High
Pressure Shutdown
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
1
BV263
Diagnostic:
Compressor 1 High
Superheat
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
1
BV264
Diagnostic:
Compressor 1 Low
Superheat
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
1
BV265
Diagnostic:
Compressor 1 Safety
Circuit Alarm
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
0
BV266
Diagnostic:
Compressor 1 Suction
Pressure Sensor
Failure
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
1
BV267
Diagnostic:
Compressor 1 Suction
Temperature Sensor
Failure
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
1
BV270
Diagnostic:
Compressor 2
Discharge Pressure
Sensor Failure
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 1 Failure Reset or Power Cycle.
1
BV271
Diagnostic:
Compressor 2 Frostat
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
1
BV272
Diagnostic:
Compressor 2 High
Pressure Shutdown
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
1
BV273
Diagnostic:
Compressor 2 High
Superheat
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
1
BV274
Diagnostic:
Compressor 2 Low
Superheat
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
1
BV275
Diagnostic:
Compressor 2 Safety
Circuit Alarm
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
1
BV276
Diagnostic:
Compressor 2 Suction
Pressure Sensor
Failure
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
1
BV277
Diagnostic:
Compressor 2 Suction
Temperature Sensor
Failure
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 2 Failure Reset or Power Cycle.
1
BV280
Diagnostic:
Compressor 3
Discharge Pressure
Sensor Failure
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
1
BV281
Diagnostic:
Compressor 3 Frostat
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
1
BV282
Diagnostic:
Compressor 3 High
Pressure Shutdown
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
1
BV283
Diagnostic:
Compressor 3 High
Superheat
Open = Normal
Closed = Failure
Latching Diagnostic. Cleared with
Comp 3 Failure Reset or Power Cycle.
0