EasyManuals Logo

Trane Tracer ZN511 User Manual

Trane Tracer ZN511
87 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
Wiring requirements and options
CNT-SVX06B-EN 39
Wiring requirements and options
Table 11 shows required controller inputs for minimal proper operation of
all 1 heat/1 cool applications.
Figure 10 on page 41 through Figure 14 on page 45 show typical applica-
tions that include all required and all optional components for 1 heat/1
cool applications.
Table 11. Required controller inputs for all 1 heat/1 cool applications
Function Input source
For more information,
see:
24 Vac power Terminals: GND, 24 V AC power wiring” on
page 8
Zone temperature Terminals: ZN, GND
or communicated
“ZN: Zone tempera-
ture” on page 36
Entering water temper-
ature—required only
for two-pipe and four-
pipe fan coil units with
auto changeover
Terminal: AI1
or communicated
AI1: Entering water
temperature sam-
pling” on page 37

Table of Contents

Other manuals for Trane Tracer ZN511

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer ZN511 and is the answer not in the manual?

Trane Tracer ZN511 Specifications

General IconGeneral
BrandTrane
ModelTracer ZN511
CategoryController
LanguageEnglish

Related product manuals