Electrical Requirements
46 CLCH-SVX009A-EN
Figure 41. Typical dual fan VFD wiring schematic
DEVICE DESCRIPTION ZONE
1Q1 UNIT DISCONNECT SWITCH
15
1T1 CONTROL TRANSFORMER
31
1X1 POWER DISTRIBUTION BLOCK 20
2M1 MOTOR 1
43
2M2 MOTOR 2
50
9B1 MOTOR OVERLOAD RELAY
43
9B2 MOTOR OVERLOAD RELAY
50
9F1 VFD FUSE
20
9F2 VFD FUSE
22
9F3 VFD FUSE
24
9F4 MOTOR FUSE
43
9F5 MOTOR FUSE
44
9F6 MOTOR FUSE
45
9F7 MOTOR FUSE
50
9F8 MOTOR FUSE
51
9F9 MOTOR FUSE
52
9T1 VFD
20
2M1
M
3
2M2
M
3
9F4
9F5
9F6
9F7
9F8
9F9
9F1
9F2
9F3
400A
8A
9A
405A
10A
10A
11A
14A
13A
13A
16A
16A
20B
21A
24B
10B
,B
13B
,B
16B
,B
18B
9B1
1L1
2T1
3L2
4T2
5L3
6T3
12B
15B
17A
9B2
1L1
2T1
3L2
4T2
5L3
6T3
19A
22B
23A
1Q1
7A
L3
L2
L1
1X1
6A
6A
5A
5A
4A
4A
4C
5C
6C
BLK
BLK
RED
RED
1T1
24V
208V
1T1
24V
1T1
24V
1T1
24V
12A
15A
18A
20A
22A
24A
6B
5B
4B
9B29B1
406A
9T1
GND
COMM5+ 68
COMM5- 69
FAULT+ 01
FAULT- 02
L3
L2
L1
18 RUN
12 +24VDC
53 REF IN
55 COM
W/98 V/97 U/96
5
5
5
6
6
YEL BLU
404B
403B
409B
410B
401B 401B
402B 402B
407B
408B
196001410005-61196001410005-60
196001410005-40
196001410005-39
196001410005-42
196001410005-41
196001410005-46
196001410005-45
196001410005-44
196001410005-43
SPLICE
SPLICE
SPLICE
SPLICE
SPLICE
SPLICE
DEVICE PREFIX LOCATION CODE
AREA
1
MAIN CONTROL PANEL
2
SUPPLY FAN & COIL SECTION
3
FILTER SECTION
4
MIXING BOX SECTION
5
COIL ACCESS SECTION
6
EXTERNAL PIPING
7
FIELD INSTALLED DEVICE
8
VFD CONTROL PANEL9
LOCATION
ELECTRIC HEAT CONTROL BOX
INSET B
BLK
BLU YEL
ORG
230V
BLK
BLU YEL
BLK/RED
460V
BLK
BLU YEL
RED
575V
MOTOR HPVOLTAGE FUSE CLASS
208/230 3 JJN-50 T
208/230 5 JJN-80 T
208/230 7.5 JJN-100 T
208/230 10 JJN-100 T
460 3 LP-CC-25 CC
460 5 LP-CC-25 CC
460 7.5 JJS-50 T
460 10 JJS-50 T
460 15 JJS-80 T
575 3 LP-CC-20 CC
575 5 LP-CC-20 CC
575 7.5 LP-CC-30 CC
575 10 LP-CC-30 CC
575 15 JJS-80 T
VFD FUSE - 9F1, 9F2, 9F3
MOTOR HPVOLTAGE FUSE CLASS
208/230 3 LP-CC-20 CC
208/230 5 LP-CC-30 CC
208/230 7.5 LPJ-40SP J
208/230 10 LPJ-50SP J
460 3 LP-CC-10 CC
460 5 LP-CC-12 CC
460 7.5 LP-CC-20 CC
460 10 LP-CC-20 CC
460 15 LPJ-35SP J
575 3 LP-CC-6 CC
575 5 LP-CC-10 CC
575 7.5 LP-CC-15 CC
575 10 LP-CC-20 CC
575 15 LP-CC-25 CC
MOTOR FUSE-9F4 THRU 9F9
1B1 - 28
1B2 - 28
NOTES:
1. UNLESS OTHERWISE NOTED ALL SWITCHES ARE
SHOWN AT 25 C (77 F), AT ATMOSPHERIC
PRESSURE, AT 50% RELATIVE HUMIDITY, WITH ALL
UTILITIES TURNED OFF, AND AFTER A NORMAL
SHUTDOWN HAS OCCURED.
2. DASHED LINES INDICATE RECOMMENDED FIELD
WIRING BY OTHERS. DASHED LINE ENCLOSURES
AND/OR DASHED DEVICE OUTLINES INDICATE
COMPONENETS PROVIDED BY THE FIELD. PHANTOM
LINE ENCLOSURES INDICATE ALTERNATE CIRCUITRY
OR AVAILABLE SALES OPTIONS. SOLID LINES
INDICATE WIRING BY TRANE.
3. NUMBERS ALONG THE RIGHT SIDE OF THE SCHEMATIC
DESIGNATE THE LOCATION OF CONTACTS BY LINE
NUMBER. AN UNDERLINED NUMBER INDICATES A
NORMALLY CLOSED CONTACT. AN OPEN ARROWHEAD
BELOW THE LINE NUMBER POINTING UPWARD INDICATES
A TIMED CONTACT WHICH BEGINS TIMING WHEN
ENERGIZED.
4. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH
THE NATIONAL ELECTRICAL CODE, STATE, AND
LOCAL REQUIREMENTS. OTHER COUNTRIES
APPLICABLE NATIONAL AND/OR LOCAL REQUIREMENTS
SHALL APPLY. FIELD CONDUCTORS SHALL HAVE
INSULATION RATING NOT LESS THAN 600V COPPER
CONDUCTORS ONLY.
CONTROL TRANSFORMER SHOWN FOR 208V PRIMARY.
FOR 230V, 460V, OR 575V PRIMARY REFER TO INSET "B".
FAULT RELAY CONTACTS STATE SHOWN WITH DRIVE
CONTROLLER DE-ENERGIZED OR FAULTED.