128
RT-SVX34R-EN
Table 72. Supply fan VFD programming parameters (continued)
Menu ID Name FC Unit
Analog In/Out
6-14
Terminal 53 Low Ref./Feedb.
Value
35
6-15
Terminal 53 High Ref./Feedb.
Value
60
Special Function
14-01
Switching Frequency
8.0 kHz (drive dependant, set to
5kHz if 8kHz not available)
14-11 (TR200 only) Mains Voltage at Mains Fault
391V for 460V 60Hz unit, leave
at default otherwise
14-12 Function at Mains Imbalance Derate
14-20 Reset Mode Automatic reset x 5
14–27 Action at Inverter Fault
Warning
14-50 RFI Filter Off
14-60 (TR200 only)
Function at Over
Temperature
Derate
14-61 (TR200 only)
Function at Inverter Overload Derate
Note: For 50Hz units parameters 0-06 Grid Type (TR150s only) and 1-23 Motor Freq will need to be set accordingly.