What to do if Trane Air Conditioner CPR1 and ODM1 will not operate?
- AAndrew YoungAug 23, 2025
If CPR1 and ODM1 on your Trane Air Conditioner aren't operating, the issue might stem from: * **No power to CC1 coil:** Check the wiring, terminals, and applicable controls (CCB1, HPC1, TDL1, WTL1, LPC1). * **Defective CC1 coil:** Inspect the CC1 coil. If it's open or shorted, replace CC1. * **Defective CC1 contacts:** If 24 VAC is present at the CC1 coil, verify contact closure. * **Defective RTRM:** If 24 VAC is not present at the CC1 coil, reset the Cool Failure by cycling the main power disconnect switch. Verify the system MODE is set for cooling operation. If no controls have opened, and CC1 will not close, replace RTRM. * **LPC1 has tripped:** Conduct a leak check, repair, evacuate, and recharge as needed. Also, check the LPC1 operation.