RT-SVX34C-EN 47
Installation Electrical
Remote Minimum Position Potentiometer (BAYSTAT023*)
This device can be used with units with an economizer. It allows the operator to remotely set the
position of the economizer dampers from 0% to 50% of fresh air entering the space.
Space Temperature Averaging
Space temperature averaging is accomplished by wiring a number of remote sensors in a series/
parallel circuit.
The fewest number of sensors required to accomplish space temperature averaging is four.
Example #1 illustrates two series circuits with two sensors in each circuit wired in parallel. Any
number squared, is the number of remote sensors required. Example #2 illustrates three sensors
squared in a series/parallel circuit. NSB panel remote sensors must use twisted/shielded cable.
Figure 31. Remote Minimum Position Potentiometer (BAYSTAT023)