EasyManua.ls Logo

Trane Voyager Commercial - Installation Electrical Procedures; Hazardous Voltage Warnings; Disconnect Switch External Handle Operation; Main Power Wiring Guidelines

Trane Voyager Commercial
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
RT-SVX34R-EN
Installation Electrical
WWAARRNNIINNGG
HHaazzaarrddoouuss VVoollttaaggee!!
FFaaiilluurree ttoo ddiissccoonnnneecctt ppoowweerr bbeeffoorree sseerrvviicciinngg ccoouulldd
rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy..
DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee
ddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr
lloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr
ccaann nnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd.. VVeerriiffyy tthhaatt nnoo
ppoowweerr iiss pprreesseenntt wwiitthh aa vvoollttmmeetteerr..
Disconnect Switch External
Handle (Factory Mounted
Option)
Units ordered with the factory mounted disconnect
switch come equipped with an externally mounted
handle. This allows the operator to disconnect power
from the unit without having to open the control panel
door. The handle location and its three positions are
shown below;
ON - Indicates that the disconnect switch is closed,
allowing the main power supply to be applied at the
unit.
OFF - Indicates that the disconnect switch is open,
interrupting the main power supply at the unit.
OPEN COVER/RESET - Turning the handle to this
position releases the handle from the disconnect
switch, allowing the control panel door to be
opened.
Once the door has been opened, it can be closed with
the handle in any one of the three positions outlined
above, provided it matches the disconnect switch
position. The handle can be locked in the “OFF”
position. While holding the handle in the “OFF”
position, push the spring loaded thumb key, attached
to the handle, into the base slot. Place the lock shackle
between the handle and the thumb key. This will
prevent it from springing out of position.
Figure 19. Disconnect switch
Disconnect switch
external handle
Locking
slot (OFF)
Locking
thumb key
C
ontr
o
l
Pa
n
e
l
Compressor Panel
An overall layout of the field required power wiring is
illustrated in . To insure that the unit supply power
wiring is properly sized and installed, follow the
guidelines outlined below.
NNoottee:: All field installed wiring must conform to NEC
guidelines as well as State and Local codes.
Verify that the power supply available is compatible
with the unit's name plate ratings for all components.
The available power supply must be within 10% of the
rated voltage stamped on the nameplate. Use only
copper conductors to connect the 3-phase power
supply to the unit.
Main Power Wiring
WWAARRNNIINNGG
PPrrooppeerr FFiieelldd WWiirriinngg aanndd GGrroouunnddiinngg
RReeqquuiirreedd!!
FFaaiilluurree ttoo ffoollllooww ccooddee ccoouulldd rreessuulltt iinn ddeeaatthh oorr
sseerriioouuss iinnjjuurryy..
AAllll ffiieelldd wwiirriinngg MMUUSSTT bbee ppeerrffoorrmmeedd bbyy qquuaalliiffiieedd
ppeerrssoonnnneell.. IImmpprrooppeerrllyy iinnssttaalllleedd aanndd ggrroouunnddeedd
ffiieelldd wwiirriinngg ppoosseess FFIIRREE aanndd EELLEECCTTRROOCCUUTTIIOONN
hhaazzaarrddss.. TToo aavvooiidd tthheessee hhaazzaarrddss,, yyoouu MMUUSSTT ffoollllooww
rreeqquuiirreemmeennttss ffoorr ffiieelldd wwiirriinngg iinnssttaallllaattiioonn aanndd
ggrroouunnddiinngg aass ddeessccrriibbeedd iinn NNEECC aanndd yyoouurr llooccaall//
ssttaattee//nnaattiioonnaall eelleeccttrriiccaall ccooddeess..
NNOOTTIICCEE
UUssee CCooppppeerr CCoonndduuccttoorrss OOnnllyy!!
FFaaiilluurree ttoo uussee ccooppppeerr ccoonndduuccttoorrss ccoouulldd rreessuulltt iinn
eeqquuiippmmeenntt ddaammaaggee aass tthhee eeqquuiippmmeenntt wwaass nnoott
ddeessiiggnneedd oorr qquuaalliiffiieedd ttoo aacccceepptt ootthheerr ttyyppeess ooff
ccoonndduuccttoorrss..

Table of Contents

Other manuals for Trane Voyager Commercial