20
RT-SVX34R-EN
Figure 14. Center of gravity
X
Y
Z (see note 2)
Table 4. Approximate units operating weights lbs./kg
Unit
Model
(60Hz/
50Hz)
Basic Unit Weights
YC Low
Heat
YC High
Heat
TC TE
330/275 3720 / 1687 4150 / 1882 3590 / 1628 3610 / 1637.5
360/305 3795 / 1721 4225 / 1916 3665 / 1662 3685 / 1671.5
420/350 3876 / 1758 4306 / 1953 3746 / 1699 3766 / 1708
480/400 4825 / 2189 4950 / 2245 4565 / 2071 4600 / 2086.5
600/500 5077 / 2303 5202 / 2360
4827 /
2189.5
4852 / 2201
Note: Weights shown represent approximate operating weights and
have a ±10% accuracy. To calculate weight for a specific unit
configuration, utilize TOPSS™ or contact the local Trane® sales
representative. ACTUAL WEIGHTS ARE STAMPED ON THE UNIT
NAMEPLATE.
Table 5. Point loading average weight— lbs./kg
Unit
Model
(60Hz/
50Hz)
A B C D E F
330/275
852 /
386
695 /
315
754 /
342
740 /
335
602 /
273
504 /
228
360/305
878 /
398
681 /
309
750 /
340
713 /
323
577 /
262
622 /
282
420/350
841 /
381
842 /
382
669 /
303
735 /
333
582 /
264
634 /
287
480/400
835 /
378
869 /
394
950 /
431
748 /
339
769 /
349
776 /
352
600/500
882 /
400
931 /
422
954 /
433
740 /
336
844 /
382
847 /
384
Notes:
1. Point loading is identified with corner A being the corner
with the compressors. As you move clockwise around the
unit as viewed from the top, mid-point B, corner C, corner
D, mid-point E and corner F.
2. Point load calculations provided are based on the unit
weight for YC high heat gas models.
UUnniitt DDiimmeennssiioonnss aanndd WWeeiigghhttss

Table of Contents