EasyManua.ls Logo

Trane Voyager Commercial - Page 30

Trane Voyager Commercial
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
RT-SVX34R-EN
Table 11. Electrical service sizing data 275–350 units 50Hz
Model
Elec.
Specs
Comp. Std Eff
Comp. High Eff,
eStage
Fan Motors
Supply
Condenser Exhaust
No/
Ton
RLA
(Ea.)
LRA
(Ea.)
No/
Ton
RLA
(Ea.)
LRA
(Ea.)
HP
(kW)
FLA No
HP
(kW)
FLA
(Ea.)
50% 100%
HP
(kW)
FLA
(Ea.)
No.
TC/TE/
YC*275
380/415/
50/3
1/10,
1/11
21.0/
23.0
147/
158
1/6, 2/
9
14.1,
16.8
98, 142
7.5
(5.6),
10
(6.8)
12.1/
11.5,
15.2/
14.6
3
0.75
(0.56)
4.4 1 2
0.75
(0.56)
1.7
TC/TE/
YC*305
380-415/
50/3
0.1818 23 158
1/6, 2/
10
14.1,
18.6
98, 142
7.5
(5.6),
10
(6.8)
12.1/
11.5,
15.2/
14.6
3
0.75
(0.56)
4.4 1 2
0.75
(0.56)
1.7
TC/TE/
YC*350
380-415/
50/3
1/11,
1/12
23.0/
27.5
158/
197
1/6, 2/
11
14.1,
19.2
98, 147
7.5
(5.6),
10
(6.8),
15
(10.5)
12.1/
11.5,
15.2/
14.6,
22.0/
23.0
3
0.75
(0.56)
4.4 1 2
0.75
(0.56)
1.7
Notes:
1. All customer wiring and devices must be installed in accordance with local and national electrical codes.
2. Allowable voltage range for the 380V unit is 342-418V, allowable voltage range for the 415V unit is 373-456.
3. 100% Power Exhaust is with or without Statitrac™.
4. All condenser fan motors are single phase.
Table 12. Electrical service sizing data 400–500 50Hz
Model
Elec.
Specs
Comp. Std Eff VAV
Only
Comp. Std Eff CV &
High Eff eStage
Fan Motors
Supply
Condenser Exhaust
No/
Ton
RLA
(Ea.)
LRA
(Ea.)
No/
Ton
RLA
(Ea.)
LRA
(Ea.)
HP
(kW)
FLA No
HP
(kW)
FLA
(Ea.)
50% 100%
HP
(kW)
FLA
(Ea.)
No.
TC/TE/
YC*400
380-415/
50/3
1/11,
1/17
23.0/
34.0
158/
215
1/8, 2/
13
14.1,
23.0
98, 158
10
(6.8),
15
(10.5)
15.2/
14.6,
22.0/
23.0
4
0.75
(0.56)
4.4 1 2
1.0
(0.75)
2.5
TC/TE/
YC*500
380-415/
50/3
2/11,
1/12
23.0/
27.5
158/
197
1/10,
2/15
18.6,
27.5
142,
155
10
(6.8),
15
(10.5),
20
(12.8)
15.2/
14.6,
22.0/
23.0,
28.0/
28.0
4
0.75
(0.56)
4.4 1 2
1.0
(0.75)
2.5
Notes:
1. All customer wiring and devices must be installed in accordance with local and national electrical codes.
2. Allowable voltage range for the 380V unit is 342-418V, allowable voltage range for the 415V unit is 373-456.
3. 100% Power Exhaust is with or without Statitrac™.
4. All condenser fan motors are single phase.
IInnssttaallllaattiioonn EElleeccttrriiccaall