RT-SVX34R-EN
73
Table 45. Test mode states for CV units with modulating hot gas reheat and modulating heat
TEST
STEP MODE FAN ECON
COMP
1
COMP
2
COMP
3
HEAT
OUTPUT
PUMP-
OUT
COOL
VALVE
RE-
HEAT
VALVE
VAV
BOX
1 FAN ON ON MIN OFF OFF OFF OFF OFF 100% 0% ON
2
ECONO-
MIZER
ON OPEN OFF OFF OFF OFF OFF 100% 0% ON
3 COOL 1 ON MIN ON OFF OFF OFF
IN-
CONTROL
100% 0% ON
4 COOL 2 ON MIN ON ON OFF OFF
IN-
CONTROL
100% 0% ON
5 COOL 3 ON MIN ON ON ON OFF
IN-
CONTROL
100% 0% ON
6 REHEAT ON MIN ON ON ON OFF
IN-
CONTROL
50% 50% ON
7 HEAT 1 ON MIN OFF OFF OFF 50% OFF 100% 0% ON
8 HEAT 2 ON MIN OFF OFF OFF 100% OFF 100% 0% ON
9 RESET
Notes:2 & 3 stage standard efficiency units (excluding 40-50T Std Efficiency CV):
1. For 27.5-35T units, both compressors will be energized during the Cool 2 Step. For 40-50T units, only Compressor 2 will be energized
during the Cool 2 Step.
2. The Reheat Pumpout relay will be energized any time the Reheat circuit is energized in active Cooling Mode.
3. For units with Statitrac installed, the Exhaust Damper will track the Economizer position during Service Test Mode and the Exhaust Fan
will be energized once the Economizer rises above the Exhaust Enable Setpoint.
4. Heating will not be energized during Service Test until the 6 minute VAV Box ON timer has expired.
Notes:5 stage high efficiency units (including 40-50T Std Efficiency CV):
1. Compressor 1 is the smaller compressor on the circuit.
2. Condenser fans are controlled as defined for normal operation.
3. Exhaust fan operates as defined for normal operation based on economizer position.
4. When Compressor 1 is energized with either C1, C2, or with both for 30 minutes continuously, C3 will be required to de-energize for 30