Programming Descriptions
Section [005] System Times
After entering Section [005], enter the 2-digit subsection number for the desired partition and program the Entry Delay 1, Entry Delay 2 and Exit Delay
for each active partition on the system. Valid entries are from [001] to [255] (in seconds). Enter subsection [09] to program the Bell Cut-Off Time. Valid
entries are from [001] to [255] (in minutes).
Section [006] Installer Code
The default Installer Code is [5555] or [555555] if 6-Digit Access Codes is enabled.
Section [007] Master Code
The default Master Code is [1234] or [123456] if 6-digit Access Codes is enabled.
Section [008] Maintenance Code
The default Maintenance Code is [AAAA] (not programmed). This code can only be used to arm and disarm partitions.
Section [009] to [011] PGM Outputs
The PC1616 and PC1832 have two on-board PGM outputs (PGM1 and PGM2). The PC1808 and PC1864 have four on-board PGM outputs (PGM1 to
PGM4). The panel has the capacity for up to 14 PGM outputs (8 additional low-current PGM outputs with PC5208 module, 4 additional high-current
PGM outputs with a PC5204 module).
PGM Output Options:
[31]
Day Zone: Instant alarm when system is armed, keypad buzzer (no alarm) when system is disarmed
[32]
Instant Stay/Away: Similar to ‘Instant’ except panel will auto-bypass the zone if Armed in the Stay mode
[35]
24-Hour Bell/Buzzer: Instant alarm when violated, system will activate bell output if armed, keypad buzzer if disarmed
[36]
24-hr. Non-Latching Tamper Zone: Instant tamper condition when violated. Active in both the armed and disarmed state.
[37]
Night Zone: Functions like Interior Stay/Away but will remain bypassed if the user presses [][1] to re-activate Stay/Away zones when
armed in the Stay mode
[41] 24 Hr. Carbon Monoxide: This zone type is used with a hardwired CO detector. This zone definition has a distinct bell cadence in
the event of an alarm. The cadence of this alarm is 4 cycles of 100ms on/off pulses, followed by a 5-second pause, and then repeated.
After 4 minutes, the 5-second pause is extended to 60 seconds in duration. The bell is silenced when an access code is entered or the
bell times out (see your CO detector instruction sheet for more details).
[81] 24 Hr. Carbon Monoxide (Wireless): This zone type is used with a wireless CO detector. This zone definition has a distinct bell
cadence in the event of an alarm. The cadence of this alarm is 4 cycles of 100ms on/off pulses, followed by a 5-second pause, and
then repeated. After 4 minutes, the 5-second pause is extended to 60 seconds in duration. The bell is silenced when an access code is
entered or the bell times out.
[87]
Delayed 24-Hour Fire (Wireless/Addressable): Same as Delayed 24-Hour Fire (Hardwire) but must be used for wireless or addressable
smoke detectors
[88]
Standard 24-Hour Fire (Wireless/Addressable): Same as Standard 24-Hour Fire (Hardwire) but must be used for wireless or addressable
smoke detectors
Option
Description
[00] For Future Use
[01] Fire and Burglary: Output will activate (steady for burglary, pulsing for fire) if an alarm occurs on the selected partition
[02] For Future Use
[03] Sensor Reset: Output will normally be active and deactivate for 5 seconds when a [][7][2] fire reset command is entered or when an Auto-
Verify Fire alarm is detected
[04] 2-Wire Smoke: Configures PGM2 as 2-wire smoke detector input (PGM2 only)
[05] Armed Status: Output will activate when all of the selected partitions are armed
[06] Ready Status: Output will activate when all the selected partitions are in the Ready state (Ready light ON)
[07] Keypad Buzzer Follow: Output will activate and follow the keypad buzzer for the selected partition when the following events occur; entry
delay, door chime, audible exit delay, automatic arming pre-alert, 24-Hour Supervisory Buzzer zone alarm
[08] Courtesy Pulse: Output will activate during entry/exit delay if the selected partition is armed – will remain active for an additional 2
minutes after the entry or exit delay expires
[09] System Trouble: Output will activate when any selected trouble condition is present
[10] Latched System Event (Strobe): Output will activate when a selected condition occurs on any selected partition. Note output can be
programmed to follow timer
[11] System Tamper: Output will activate when any tamper condition is present
[12] TLM and Alarm: Output will activate if a telephone line trouble is present and then an alarm occurs
[13] Kissoff: Output will activate for 2 seconds when a valid kissoff is received from the central station