EQUIPMENT: T1200
PUBLICATION: 19A-4-O
ISSUE No. & DATE: 3 06/09
© 2006 Tyco Safety Products PAGE 13 of 13
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
6. Routine Testing and maintenance
See T1200 Log Book for details.
7. User responsibilities
See T1200 Log Book for details
8. T1200 Isolate/De-Isolate/Test Mode Select Flowchart
CURSOR Sequence:
Start
T1200 Panel
Controls not Enabled
Turn ACCESS
CONTROLS keyswitch
to ‘1’
T1200 Panel
Controls Enabled
Turn ACCESS
CONTROLS keyswitch
to ‘1’
Press SELECT ON/OFF
button
T1200 Panel
SELECT mode active,
Select ON/OFF LED
illuminated
T1200 Panel
SELECT cursor flashes
zone 1 Fault LED
Press ENABLE button Press DISABLE button Press TEST button
Press SELECT ON/OFF
button
Press SELECT
button
Press SELECT
button
Zone 1 Fault LED
Zone 2 Fault LED
Zone n Fault LED (n=4,16 or 32
depending on panel)
Sounder Fault/Disabled & Test LEDs
Fire Protection Fault/Disabled LED
Fire Routing Fault/Disabled LED
Fault Routing Fault/Disabled LED
T1200 Panel
SELECT cursor moves
to next LED
T1200 Panel
SELECT cursor moves
to previous LED
T1200 Panel
Selected Circuit returned to
normal operation.
LED pulses ‘OFF/flash’
(changes to OFF when cursor
is removed)
T1200 Panel
Selected Circuit Disabled.
LED pulses ‘ON/flash’
(changes to ON when cursor is
removed)
T1200 Panel
Selected Circuit in Test mode.
If Zone circuit then Zone Fault
LED pulses ‘ON/flash’
(changes to ON when cursor is
removed).
If Sounders then Sounder Test
LED is ON.
T1200 Panel
SELECT mode inactive.
SELECT cursor clears.
SELECT LED clears.