C 59 SELF Self tuning enabling no = The instrument does not perform the self-
tuning
YES = The instrument is performing the self-
tuning
No
A 62 Pb Proportional band 1... 9999 (E.U.) See
page 7
A 63 ti Integral time 0 (oFF) ... 9999 (s) See
page 7
A 64 td Derivative time 0 (oFF) ... 9999 (s) See
page 7
C 65 Fuoc Fuzzy overshoot control 0.00... 2.00 1
C 69 rS Manual reset (Integral pre-load) -100.0... +100.0 (%) 0.0
A 70 Str.t Servomotor stroke time 5...1000 seconds See
page 7
A 71 db.S Servomotor dead band 0...100% 5
C 72 od Delay at power up 0.00 (oFF) ... 99.59 (hh.mm) oFF
SP Group - Set point parameters
Liv N° Param Description
Values
Default
C 76 nSP Number of used set points 1... 4 2
A 77 SPLL Minimum set point value -1999 ... SPHL See
page 7
A 78 SPHL Maximum set point value SPLL ... 9999 See
page 7
O 79 SP Set point 1 SPLL ... SPLH See
page 7
C 80 SP 2 Set point 2 SPLL ... SPLH 60
83 A.SP Selection of the active set point "SP" ... " nSP" SP
C 84 SP.rt Remote set point type RSP = The value coming from serial link is used
as remote set point
trin = The value will be added to the local set
point selected by
A.SP and the sum becomes the operative set
point
PErc = The value will be scaled on the input
range and this value will be used as remote SP
trin
C 85 SPLr Local/remote set point selection Loc = Local
rEn = Remote
Loc
C 86 SP.u Rate of rise for POSITIVE set point
change (ramp UP)
0.01... 99.99 (inF) Eng. units per minute inF
C 87 SP.d Rate of rise for NEGATIVE set point
change (ramp DOWN)
0.01... 99.99 (inF) Eng. units per minute inF
PAn Group - Operator HMI
Liv N° Param Description
Values
Default
C 118 PAS2 Level 2 password (limited access level) oFF (Level 2 not protected by password)
1... 200
20
C 119 PAS3 Level 3 password (complete
configuration level)
3... 300 30
C 120 PAS4 Password livello (livello configurazione a
codice)
201... 400 300
C 121 uSrb button function during RUN TIME nonE = No function
tunE = Auto-tune/self-tune enabling. A single
press (longer than 1 second)
starts the auto-tune
oPLo = Manual mode. The first pressure puts the
instrument in manual mode
(OPLO) while a second one puts the instrument
in Auto mode
tunE