AAc = Alarm reset
ASi = Alarm acknowledge
chSP = Sequential set point selection
St.by = Stand by mode. The first press puts the
instrument in stand by
mode while a second one puts the instrument in
Auto mode.
Str.t = Timer run/hold/reset
P.run = Program run
P.rES = Program reset
P.r.H.r = Program run/hold/reset
C 122 diSP Display management Spo = Operative set point SPo
C 123 di.cL Display colour 0 = The display colour is used to show the actual
deviation (PV - SP)
1 = Display red (fix)
2 = Display green (fix)
3 = Display orange (fix)
2
125
diS.t Display Timeout -- oFF (display always ON)
-- 0.1... 99.59 (mm.ss)
oFF
C 126 fiLd Filter on the displayed value -- oFF (filter disabled)
-- From 0.0 (oFF) to 20.0 (E.U.)
oFF
C 128 dSPu Instrument status at power ON AS.Pr = Starts in the same way it was prior to the
power down
Auto = Starts in Auto mode
oP.0 = Starts in manual mode with a power
output equal to zero
St.bY = Starts in stand-by mode
Auto
C 129 oPr.E Operative modes enabling ALL = All modes will be selectable by the next
parameter
Au.oP = Auto and manual (OPLO) mode only will
be selectable by the next parameter
Au.Sb = Auto and Stand-by modes only will be
selectable by the next parameter
ALL
C 130 oPEr Operative mode selection If oPr.E = ALL: - Auto = Auto mode
- oPLo = Manual mode
- St.bY = Stand by mode
If oPr.E = Au.oP: - Auto = Auto mode
- oPLo = Manual mode
If oPr.E = Au.Sb: - Auto = Auto mode
- St.bY = Stand by mode
Auto
SEr Group - Serial link paramete
r
Liv N° Param Description
Values
Default
C 131 Add Instrument address -- oFF
-- 1... 254
1
C 132 bAud baud rate 1200 = 1200 baud
2400 = 2400 baud
9600 = 9600 baud
19.2 = 19200 baud
38.4 = 38400 baud
9600
C 133 trSP Selection of the value to be retransmitted
(Master)
nonE = Retransmission not used (the instrument
is a slave)
rSP = The instrument becomes a Master and
retransmits the operative set point
PErc = The instrument become a Master and it
retransmits the power output
nonE
13