BOILER RATINGS AND CAPACITIES
Table 2 Ratings and Capacities
Natural Gas & Propane (LP)
Boiler Model
Number
Input
MBH (1)
Heating
Capacity
MBH (1)
Net AHRI Rating (2)
AFUE, %
No. of
Sections
Vent Pipe
Size
Steam,
MBH
Steam,
Sq. Ft.
PEG075EID 75 62 47 195 82.2 3 5"
P EG112EID 112 93 70 292 82.4 4 5"
PEG150EID 150 125 94 391 82.6 5 6"
P EG187EID 187 156 117 488 82.8 6 7"
P EG225EID 225 188 141 587 83.0 7 7"
P EG262EID 262 219 164 685 83.2 8 7"
P EG299EID 299 250 188 782 83.4 9 7"
Heating Capacity and AFUE are based on DOE (Department of Energy) test procedures.
1.
Input rating for sea level to 2,000 ft. above sea level.
Altitudes over 2000 ft. above
sea level, reduce input rate 4% for every 1000 ft.
2. Net AHRI steam ratings shown are based on a piping and pickup allowance of 1.333.
Consult manufacturer before selecting a boiler for installations having unusual piping
and pickup requirements, such as intermittent system operation, extensive piping
systems, etc.