0020308118_05 Installation and maintenance instructions 27
7.2.6 Replacing the standard connector for the
air/flue pipe, where required
7.2.6.1 Removing the standard connector for the
air/flue pipe
A
B
C
7.2.6.2 Installing the connector for the air/flue pipe,
60/100 mm or 80/125 mm diameter
1. Remove the standard connector for the air/flue pipe.
( Section 7.2.6.1)
2. Insert the alternative connector. In doing so, pay atten-
tion to the latching lugs.
3. Turn the standard connector clockwise until it clicks
into position.
7.3 Installing the gas connection
Install the gas pipe in accordance with the recognised
rules of technology.
Remove the residues from the gas pipe by decoupling on
both sides and blowing through the gas pipe.
Use the enclosed gas isolation valve. Observe the spe-
cified flow direction.
Note
Gas isolation valves with or without test nipple
are available in the dimensions 15 to 15 mm
or 22 to 15 mm.
Condition: Gas isolation valve without test nipple
Connect the product to the gas pipe as shown in accord-
ance with the recognised rules of good engineering prac-
tice.
Condition: Gas isolation valve with test nipple (requirement for BS 6891)
1
Connect the product to the gas pipe as shown in accord-
ance with the recognised rules of good engineering prac-
tice.
Always ensure that the test nipple (1) is sealed and is
correctly checked for tightness. Tightening torque, see
appendix.
Working materials: 3 mm hex key
Purge the gas pipe before start-up.
Check the entire gas supply for tightness in accordance
with the relevant standards.
90°
90°
1
Turn the gas isolation valve (1) by a 90° rotation:
Open: Rotate by 90° anti-clockwise
Close: Rotate by 90° clockwise
Note
To isolate, only use the mechanism that is
provided by the gas isolation valve. Any
change, wear or damage to a part of the gas
isolation valve means that the fitting no longer
complies with the performance requirements
of the standard and it must be completely
replaced.

Table of Contents

Other manuals for Vaillant ecoTEC plus VU Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant ecoTEC plus VU Series and is the answer not in the manual?

Vaillant ecoTEC plus VU Series Specifications

General IconGeneral
TypeCondensing Boiler
InstallationWall-mounted
Heating circuitSealed System
ErP RatingA
FuelNatural Gas
EfficiencyUp to 94%
Modulation1:6
Warranty2-5 years (depending on model and region)
Dimensions720 x 440 x 338 mm

Related product manuals