EasyManua.ls Logo

Vaillant ecoTEC plus - Temporary Shutdown and Frost Protection

Vaillant ecoTEC plus
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installing the concentric connection to the air/flue gas system (LAS)
Installation manual for the flue pipe for ecoTEC plus 0020137851_02 19
7
7 Installing the concentric connection
to the air/flue gas system (LAS)
You require at least:
– The 87° elbow, dia. 110/160 mm
(article number 0020106380)
– An extension Ø110/160 mm (article number 0020106385)
a
Danger!
Risk of poisoning due to escaping flue
gas!
Standing condensate can damage the seals
of the flue gas pipe.
> Lay the horizontal flue pipe with a down-
ward gradient of 3° inwards. 3° corre-
sponds to a downward gradient of
approx. 50 mm per metre of pipe length.
a
Danger!
Risk of poisoning due to escaping flue
gas!
In the event of overpressure in the vertical
part of the flue gas pipe, flue gas may flow
into a unit that is not operating. The units
are not suitable for this mode of operation
and are not checked.
> Provide evidence of the functional relia-
bility of the vertical flue gas pipe in
accordance with EN 13384 using the
specifications for flue gas temperature
and flue gas mass rate from the installa-
tion instructions for the unit.
a
Danger!
Risk of injury due to damage to the
structural integrity.
The static function and fire-protective func-
tion of the shaft wall may be impaired and
may lead to a hazard to persons.
> Do not attach any fastenings using bolts,
rawl plugs, etc. directly to the shaft wall
of the air/flue gas system.
> Do not attach fastenings to primary wall-
ing or sideways to the wall.
> Observe the specifications provided by
the manufacturer of the air/flue gas
system.
B
A
7.1 Shorten the flue pipe to the length required and insert the
air pipe
Key
A Air
B Flue gas
> On the air/flue gas system, establish a connection in
accordance with the dimensions in ¬section 3. These
dimensions allow for the lateral installation of the unit or
installation directly on the primary walling.
Ceramic air/flue gas systems are usually equipped with rub-
ber sealing sleeves and have a pipe stop on the air-side
connection.
> Separate the sleeve on the flue pipe so that you can
slide the flue pipe into the seal.
> Insert the air pipe into the sleeve of the air/flue gas sys-
tem.
> Insert the flue pipe into the flue seal of the air/flue gas
system. When fitting further elements, prevent the flue
pipe from sliding into the flue gas duct.
Metal air/flue gas systems feature cylindrical supports on
the flue-gas-side. In this case, insert the concentric flue
pipe with sleeve.
i
For air/flue gas system shafts that have no
sleeves, you must secure the air pipe using mor-
tar and seal the shaft.
> If applicable, install additional extensions and elbows
starting from the wall and working towards the unit.
> Attach one fastening clamp for each extension.
> Finally, insert the elbow of the flue gas pipe into the flue
gas connection of the unit.
> Connect all connecting points of the air pipes using a
safety screw as described in ¬ section 10.