3 Commissioning checklist
6
Work Comments/settings
90 DHW req. anti-cy time 0 min.: KfW efficient house 40
60 min.: > KfW efficient house 40
91 Ch. pump overrun time 5 minutes
92 Parallel cyl. charging off
93 Menu → Installer level → Service information
94 Enter contact details Telephone number/company
95 Service date Next service on Maintenance interval: 1 year
→ End user menu Implement the settings for the end user/inform the end
user
96 Menu → Basic settings → Enter zone name → ZONE1 → Change Enter a suitable name for the zone, e.g. Heating
(In consultation with the customer)
97 Menu → Desired temperatures → ZONE1 Zone1 (name after being renamed)
98 Day temp. heating 20 °C
99 Day temp. cooling 24 °C
100 Set-back temp. heat. 15 °C
101 Room temperature Current value display
102 Menu → Time programmes → ZONE1 Changed the time schedule for Zone 1 (name after being
renamed) following consultation with the customer
Zone 1 = heating circuit 1
103 HEATING 1: Cooling Change the time schedule for cooling following consulta-
tion with the customer
104 Domestic hot water 00:00 – 00:00 (no time restriction recommended in
monoenergetic mode)
105 Circulation Change the time schedule for circulation following con-
sultation with the customer