0020291525_04 Installation and maintenance instructions 57
Code Meaning Cause
Remedy
F.517 Sensor fault: Compr. outlet temp. The sensor is not connected or the
sensor input has short-circuited
Check and, if required, replace the
sensor
Replace the wiring harness
F.519 Sensor fault: Building circuit re-
turn temp.
The sensor is not connected or the
sensor input has short-circuited
Check and, if required, replace the
sensor
Replace the wiring harness
F.520 Sensor fault: Building circuit flow
temp.
The sensor is not connected or the
sensor input has short-circuited
Check and, if required, replace the
sensor
Replace the wiring harness
F.526 Sensor fault: EEV outlet temp. The sensor is not connected or the
sensor input has short-circuited
Check and, if required, replace the
sensor
Replace the wiring harness
F.546 Sensor fault: High pressure The sensor is not connected or the
sensor input has short-circuited
Check the sensor (e.g. using an in-
stallation aid), and replace if neces-
sary
Replace the wiring harness
F.582 Fault: EEV EEV is not connected correctly or
there is a cable break to the coil
Check the plug connections and, if
required, replace the coil from the
EEV
F.585 Sensor fault: Capac. outlet temp. The sensor is not connected or the
sensor input has short-circuited
Check and, if required, replace the
sensor
Replace the wiring harness
F.703 Sensor fault: Low pressure The sensor is not connected or the
sensor input has short-circuited
Checking the sensor (e.g. using an
installation aid), and replacing it if
necessary
Replace the wiring harness
F.718 Fan unit 1: Fan blocked There is no confirmation signal stat-
ing that the fan is rotating
Check the air route and, if required,
remove any blockages
F.729 Compressor outlet temperature
too low
The compressor outlet temperature
is lower than 0 °C for more than 10
minutes or the compressor outlet
temperature is lower than -10 °C
even though the heat pump is in the
operating characteristics.
Checking the high-pressure sensor
Checking that the EEV is working
correctly
Check the condenser outlet temper-
ature sensor (supercooling)
Check whether the 4-port diverter
valve is in the intermediate position
Checking the refrigerant volume for
overfilling
F.731 High-pressure switch open Refrigerant pressure too high. The
integrated high-pressure switch
in the outdoor unit has tripped at
31.5 bar (g) or 32.5 bar (abs)
Insufficient energy output via the
condenser
Purging the building circuit
Too low a volume flow as a result
of closing single room controls in an
underfloor heating system
Check that the dirt filter that is in
place is permeable
Refrigerant flow rate too low (e.g.
electronic expansion valve defective,
4-port diverter valve is mechanically
blocked, filter is blocked). Inform
customer service.
Cooling mode: Check the fan unit for
dirt
Check the high-pressure switch and
high-pressure sensor
Reset the high-pressure switch and
carry out a manual reset on the
product.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant uniTOWER plus and is the answer not in the manual?

Vaillant uniTOWER plus Specifications

General IconGeneral
BrandVaillant
ModeluniTOWER plus
CategoryHeat Pump
LanguageEnglish

Related product manuals