EasyManuals Logo

Vaillant uniTOWER plus User Manual

Vaillant uniTOWER plus
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #58 background imageLoading...
Page #58 background image
*****INTERNAL*****30 R_D proof- 26.10.2022 / 09:15:46- VaillantGroup\DOC-agt\Brand\VIH_QW_190_6\ENG\OI-II_GB_0020291525
58 Installation and maintenance instructions 0020291525_04
Code Meaning Cause
Remedy
F.732 Compressor outlet temperature
too high
The compressor outlet temperature is
above 110 °C:
Application limits exceeded
EEV does not work or does not open
correctly
Refrigerant volume too low (frequent
defrosting due to extremely low
evaporation temperatures)
Check the compressor inlet sensor
and outlet sensor
Check the compressor outlet temper-
ature sensor (TT135)
Check the EEV (does the EEV
move to the limit stop? Use the
sensor/actuator test)
Check the refrigerant volume (see
Technical data)
Carry out a leak-tightness test
Check whether the service valves on
the outdoor unit are open.
F.733 Evaporation temperature too low Insufficient air volume flow through
the outdoor unit's heat exchanger
(heating mode) leads to an insuffi-
cient energy input in the environment
circuit (heating mode) or building cir-
cuit (cooling mode)
Refrigerant volume too low
If the building circuit contains ther-
mostatic valves, check that they are
suitable for cooling mode (check
volume flow in cooling mode)
Check the fan unit for dirt
Check the EEV (does the EEV
move to the limit stop? Use the
sensor/actuator test)
Check the compressor inlet sensor
Check the refrigerant volume
F.734 Condensation temperature too low The temperature in the heating
circuit is too low, outside of the
operating characteristics
Refrigerant volume too low
Check the EEV (does the EEV
move to the limit stop? Use the
sensor/actuator test)
Check the compressor inlet sensor
Check the refrigerant filling volume
(see technical data)
Check whether the 4-port diverter
valve is in an intermediate position
and is not correctly switched
Checking the high-pressure sensor
Check the pressure sensor in the
heating circuit
F.735 Evaporation temperature too high Temperature in the environment
circuit (heating mode) or building
circuit (cooling mode) too high for
compressor operation
Feed-in of external heat into the
environment circuit too high due to
increased fan speed
Check the system temperatures
Check the refrigerant filling volume
for overfilling
Check the EEV (does the EEV
move to the limit stop? Use
sensor/actuator test)
Check the sensor for the evaporation
temperature (depending on the
position of the 4-port diverter valve)
Check the volume flow in cooling
mode
Check the air volume flow in heating
mode
F.737 Condensation temperature too
high
Temperature in the environment
circuit (cooling mode) or building
circuit (heating mode) too high for
compressor operation
Feed-in of external heat into the
building circuit
Refrigerant circuit overfilled
Insufficient flow rate in the building
circuit
Reduce or stop the external heat
that is entering
Check the back-up heater (heats
up even though it is off in the
sensor/actuator test?)
Check the EEV (does the EEV
move to the limit stop? Use the
sensor/actuator test)
Check the compressor outlet sensor,
compressor outlet temperature
sensor (TT135) and high-pressure
sensor
Check the refrigerant filling volume
for overfilling
Check whether the service valves on
the outdoor unit are open.
Check the air volume flow in cooling
mode for sufficient flow rate
Checking the heating pump
Check the building circuit flow rate

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant uniTOWER plus and is the answer not in the manual?

Vaillant uniTOWER plus Specifications

General IconGeneral
BrandVaillant
ModeluniTOWER plus
CategoryHeat Pump
LanguageEnglish

Related product manuals