EasyManua.ls Logo

Vaillant uniTOWER plus - Page 59

Vaillant uniTOWER plus
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
*****INTERNAL*****30 R_D proof- 26.10.2022 / 09:15:46- VaillantGroup\DOC-agt\Brand\VIH_QW_190_6\ENG\OI-II_GB_0020291525
0020291525_04 Installation and maintenance instructions 59
Code Meaning Cause
Remedy
F.741 Building circuit: Return temp. too
low
– During the de-icing, the return tem-
perature falls below 13 °C
– Ensure the minimum installation
volume is maintained; if required,
install a series return cylinder
– The fault message is displayed until
the return temperature increases to
above 20 °C.
– Activate the electric back-up heater
in the product's control panel and
in the system control in order to
increase the return temperature. The
compressor is blocked while the fault
message is present.
F.752 Fault: Frequency converter –
Internal electronics fault on the in-
verter PCB
– Mains voltage outside of 70 V–282 V
–
Check the integrity of the power sup-
ply cables and compressor connec-
tion cables
The plugs must audibly click into
place.
– Check the cable
– Check the mains voltage
The mains voltage must be between
195 V and 253 V.
– Check the phases
– Replace the frequency converter, if
required
F.753 Connection fault: Freq. conv.
n.recogn.
– Missing communication between the
frequency converter and the outdoor
unit's control PCB
– Check the integrity of the wiring
harness and plug connection and,
if required, replace them
– Check the frequency converter by
actuating the compressor safety
relay
– Read the assigned parameters for
the frequency converter and check
whether values are displayed
F.755 Fault: 4-port valve position not
correct
– Incorrect position of the 4-port di-
verter valve. If, in heating mode, the
flow temperature is lower than the
return temperature in the building cir-
cuit.
– The temperature sensor in the EEV
environment circuit displays an incor-
rect temperature.
– Check the 4-port diverter valve (is an
audible switching available? Use the
sensor/actuator test)
– Check that the coil is positioned
correctly on the 4-port valve
– Check the wiring harness and plug
connections
– Check the temperature sensor in the
EEV environment circuit
F.774 Sensor fault: Air inlet temp. – The sensor is not connected or the
sensor input has short-circuited
– Check and, if required, replace the
sensor
– Replace the wiring harness
F.785 Fan unit 2: Fan blocked – There is no confirmation signal stat-
ing that the fan is rotating
– Check the air route and, if required,
remove any blockages
F.788 Building circuit: Pump fault – The electronics system of the high-
efficiency pump has detected a
fault (e.g. dry running, blockage,
overvoltage, undervoltage) and has
switched off and locked the pump.
– Switch the heat pump off for at least
30 seconds (no current)
– Check the quality of the plug contact
on the PCB
– Check that the pump functions cor-
rectly
– Purging the building circuit
– Check that the dirt filter that is in
place is permeable
F.817 Freq. converter fault: Compressor – Defect in the compressor (e.g. short
circuit)
– Defect in the frequency converter
– Connection cable to the compressor
is defective or loose
– Measure the winding resistance in
the compressor
– Measure the frequency converter
output between the three phases, (it
must be > 1 kΩ)
– Check the wiring harness and plug
connections
F.818 Freq. converter fault: Mains
voltage
– Incorrect mains voltage for operating
the frequency converter
– Shutdown via the energy supply
company
– Measure and, if required, correct the
mains voltage
The mains voltage must be between
195 V and 253 V.

Table of Contents