Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 49
Function Code: 503 Version 1
Function Type: Set Print Header Line 1, 2, 3, 4
Command Format: Inquire:
Display: <SOH>S503LLaaaaaaaaaaaaaaaaaaaa <SOH>I503LL
Computer: <SOH>s503LLaaaaaaaaaaaaaaaaaaaa <SOH>i503LL
Typical Response Message, Display Format:
<SOH>
I50301
22-05-01 14:58
1:STATION HEADER 1....
<ETX>
Typical Response Message, Computer Format:
<SOH>i503LLYYMMDDHHmmaaaaaaaaaaaaaaaaaaaa&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. LL - Header line number 1, 2, 3, 4
3. a - Header Line (20 ASCII characters from 20 Hex - 7E Hex)
4. && - Data Termination Flag
5. CCCC - Message Checksum