Serial Interface Manual
• TLS2 Monitoring Systems
Part No. 577013-767, Revision H 82
Function Code: 605 Version 1
Function Type: Set Tank 4 Point Full, 3/4, 1/2, 1/4 Volumes
Command Format: Inquire:
Display: <SOH>S605TTGGGGGGggggggGGGGGGgggggg <SOH>I605TT
or: <SOH>S605TTGGGG,gggg,GGGG,ggg
Computer: <SOH>s605TTFFFFFFFFffffffffFFFFFFFFffffffff <SOH>i605TT
Notes:
1. TT - Tank Number (Decimal, 00 = all)
2. GGGGGG - Full Height Volume, Gallons (Decimal)
3. gggggg - 3/4 Height Volume, Gallons (Decimal)
4. GGGGGG - 1/2 Height Volume, Gallons (Decimal)
5. gggggg - 1/4 Height Volume, Gallons (Decimal)
6. FFFFFFFF - Full Height Volume, Gallons (ASCII Hex IEEE float)
7. ffffffff - 3/4 Height Volume, Gallons (ASCII Hex IEEE float)
8. FFFFFFFF - 1/2 Height Volume, Gallons (ASCII Hex IEEE float)
9. ffffffff - 1/4 Height Volume, Gallons (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I60501
22-05-01 15:07
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 REGULAR UNLEADED 10000 0 0 0
<ETX>
Typical Response Message, Computer Format:
<SOH>i605TTYYMMDDHHmmTTFFFFFFFFffffffffFFFFFFFFffffffff
TTFFFFFFFFffffffffFFFFFFFFffffffff&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. FFFFFFFF - Full Height Volume, Gallons (ASCII Hex IEEE float)
4. ffffffff - 3/4 Height Volume, Gallons (ASCII Hex IEEE float)
5. FFFFFFFF - 1/2 Height Volume, Gallons (ASCII Hex IEEE float)
6. ffffffff - 1/4 Height Volume, Gallons (ASCII Hex IEEE float)
7. && - Data Termination Flag
8. CCCC - Message Checksum