Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 83
Function Code: 606 Version 1
Function Type: Set Tank 20 Point Full, 95%, 90%,...Volumes
Command Format: Inquire:
Display: <SOH>S606TTGGGGGGgggggg... <SOH>I606TT
or: <SOH>S606TTGGGG,gggg,GGGG,...
Computer: <SOH>s606TTFFFFFFFF... <SOH>i606TT
Notes:
1. TT - Tank Number (Decimal, 00 = all)
2. GGGGGGgggggg - Series of 20 Volumes, Gallons (Decimal)
3. FFFFFFFF - Series of 20 Volumes, Gallons (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I60601
22-05-01 15:07
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 REGULAR UNLEADED 10000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
<ETX>
Typical Response Message, Computer Format:
<SOH>i606TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. FFFFFFFF - Series of 20 Volumes, Gallons (ASCII Hex IEEE float)
4. && - Data Termination Flag
5. CCCC - Message Checksum

Other manuals for Veeder-Root TLS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS2 and is the answer not in the manual?

Veeder-Root TLS2 Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS2
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals