Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 85
Function Code: 608 Version 1
Function Type: Set Tank Tilt
Command Format: Inquire:
Display: <SOH>S608TTIII.hh <SOH>I608TT
Computer: <SOH>s608TTFFFFFFFF <SOH>i608TT
Notes:
1. TT - Tank Number (Decimal, 00 = all)
2. III.hh - Tank Tilt, Inches and hundredths (Decimal)
3. FFFFFFFF - Tank Tilt, Inches (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I60801
22-05-01 15:07
TANK TILT
TANK PRODUCT LABEL INCHES
1 REGULAR UNLEADED 0.00
<ETX>
Typical Response Message, Computer Format:
<SOH>i608TTYYMMDDHHmmTTFFFFFFFF
TTFFFFFFFF&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. FFFFFFFF - Tank Tilt, Inches (ASCII Hex IEEE float)
4. && - Data Termination Flag
5. CCCC - Message Checksum