EasyManua.ls Logo

Veeder-Root TLS2 - Page 88

Veeder-Root TLS2
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 85
Function Code: 608 Version 1
Function Type: Set Tank Tilt
Command Format: Inquire:
Display: <SOH>S608TTIII.hh <SOH>I608TT
Computer: <SOH>s608TTFFFFFFFF <SOH>i608TT
Notes:
1. TT - Tank Number (Decimal, 00 = all)
2. III.hh - Tank Tilt, Inches and hundredths (Decimal)
3. FFFFFFFF - Tank Tilt, Inches (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I60801
22-05-01 15:07
TANK TILT
TANK PRODUCT LABEL INCHES
1 REGULAR UNLEADED 0.00
<ETX>
Typical Response Message, Computer Format:
<SOH>i608TTYYMMDDHHmmTTFFFFFFFF
TTFFFFFFFF&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. FFFFFFFF - Tank Tilt, Inches (ASCII Hex IEEE float)
4. && - Data Termination Flag
5. CCCC - Message Checksum

Other manuals for Veeder-Root TLS2