6Setupwiththedisplayandadjustmentmodule
MINITRAC 31 • Foundation Fieldbus
41782-EN-211203
Whenaresetiscarriedout,allsettings(withonlyafewexceptions)
are reset. The exceptions are: PIN, language, SIL and HART mode.
Thefollowingresetfunctionsareavailable:
Basic settings: Resetting of the parameter adjustments to default
valuesatthetimeofshipment.Order-specicsettingsaredeleted.
Default settings: Resetting of the parameter adjustment like under
" Basic settings". In addition, special parameters are reset to default
values.Order-specicsettingsaredeleted.
Peak values of measured value: Resetting of the parameter adjust-
ments in the menu item " Setup" to the default values of the respec-
tiveinstrument.Order-specicsettingsremainbutarenottakenover
into the current parameters.
Peak values of temperature: Resetting of the measured min. and
max. temperatures to the actual measured value.
Thefollowingtableshowsthedefaultvaluesoftheinstrument.The
values apply for the application " Density". First of all you have to
select the application.
Depending on the instrument version, not all menu items may be
availableortheymaybedierentlyassigned:
Menu Menu item Default value
Setup Measurement loop name Sensor
Isotope Cs-137
Application Density
Background radiation 0ct/s
Process value unit g/cm
3
Temperature unit ° C
Adjustment min. process value 0.500g/cm
3
Adjustment max. process value 1.500g/cm
3
Inner diameter 0.20 m
Linearisation 90000ct/sand0.500g/cm
3
Damping 60 s
Real value correction 0
Reference value - Relay None
Lock adjustment Released
Reset